HomeMy WebLinkAboutInitial Plan IPZR2014004 - Project Implementation Code RequirementsHUNTINGTONBEACHFIREDEPARTMENT PROJECTIMPLEMENTATIONCODEREQUIREMENTS HUNTINGTONBEACH SEPTEMBER231d,2014 USBANKPROPERTY PLANNINGAPPLICATION# 2014-121 INITIALPLANNINGANDZONINGREVIEW0. 14-004 20002-20052BROOKHURSTAND 10026ADAMS,HUNTINGTON BEACH,CA TESS NGUYEN,ASSOCIATEPLANNER (714)374-1744/tnguyen@surfcity-hb.org STEVEEROS,FIREPROTECTIONANALYST (714)536-5531/Steve.Eros@surfcity-hb.org TO REVIEWTHE RESTRIPINGOF PARKINGSPACESINAN EXISTING PARKINGLOTOFA COMMERCIALCENTER. DATE: PROJECTNAME: PANUMBER: ENTITLEMENTS: PROJECTLOCATION: PLANNER: TELEPHONE/E-MAIL: PLANREVIEWER-FIRE: TELEPHONE/E-MAIL: PROJECTDESCRIPTION: Thefollowingis a list of coderequirementsdeemedapplicableto the proposedprojectbasedonplans receivedanddated September9th,2014. The list is intendedto assistthe applicantby identifying commoncoderequirementswhichmustbesatisfiedduringthe variousstagesof projectpermittingand implementation.A listof conditionsof approvaladoptedbythe PlanningCommissionin conjunctionwith the requestedentitlement(s),if any,will alsobe provideduponfinal projectapproval. The review commentsbeloware notto beconstruedas beingall inclusive.The projectis requiredto complywith all ofthe adoptedBuilding,Fire,and MunicipalCodesineffectat the time ofgradingand building plansubmittalfor permitissuance.Ifyou haveanyquestionsregardingthese requirements,please contactthe PlanReviewer-Fire:SteveEros,FireProtectionAnalyst. PRIORTO DEMOLITION,SITEDEVELOPMENT,BUILDINGPERMITS,AND/OR CONSTRUCTION,THEFOLLOWINGSHALLBE REQUIRED: FireApparatus Access Thefollowingitemsshall becompletedpriorto issuanceofa certificateof occupancy. The Existing Fire Access Roads shall be maintained so their current widths do not diminish. There are existing access roads on the north and west side of the 20002 Brookhurst building that do not comply with City Specification # 401,MinimumStandardsfor FireApparatusAccess. These roads widths are acceptable, but shall not diminish any further than the 20 foot and 22 foot widths. The other access road widths on the property that are 26 and 29 feet shall not diminish is size either. The existing turning radii shall not be diminished from the restriping of Page2 of 4 the parkingspaces nearthe20002Brookhurstproperty. Ifthe turningradiusin anyareais altereditwill needto complywith the radiirequirementsstatedin CitySpecification# 401, MinimumStandardsforFireApparatusAccess.Theturningradiiwould requirefor cleartravel of a minimumof 17feet innerradiusand45 feetouterradiuson allcorners.(FD) No Parking shall be allowedinthe designated24footwidefire apparatusaccessroador supplementalfire accessperCitySpecification# 415. ForFireDepartmentapproval,reference anddemonstratecompliancewith CitySpecification# 415 MinimumStandardsfor Fire ApparatusAccess onthe plans.(FD) Fire Lanes,as determinedbythe Fire Department,shall be posted,marked,and maintained perCitySpecification#415,FireLanesSignageandMarkingson Private,Residential, Commercialand IndustrialProperties.Thesiteplanshallclearlyidentifyall redfire lanecurbs, bothin locationand lengthof run.The locationof fire lanesignsshallbe depicted.Noparking shallbeallowedin thedesignated24 footwidefire apparatusaccessroador supplementalfire accessperCitySpecification# 415. For FireDepartmentapproval,referenceanddemonstrate compliancewith CitySpecification# 401 MinimumStandardsfor FireApparatusAccessonthe plans.(FD) FireProtectionSystems Thefollowingitemsshall becompletedpriorto issuanceofa certificateof occupancy. Fire Extinguishers shallbe installedand locatedin allareasto complywith HuntingtonBeach FireCodestandardsfoundin CitySpecification#424.The minimumrequireddry chemicalfire extinguishersize is 2A 10BCandshall be installedwithin75feettraveldistanceto allportionsof the building.Extinguishersare requiredto beservicedor replacedannually.(FD) Fire Alarm System isrequiredto be modifiedto accommodatethe requirementsofthe new occupancies/floorplans. Ifbuildingdoes nothavea fire alarmsystem,a newfire alarmsystem is not required. For FireDepartmentapproval,shopdrawingsshallbe submittedto the Fire Departmentas separateplansfor permitsandapproval.ForFireDepartmentapproval, referenceand demonstratecompliancewith CFCChapter9 and NFPA72on the plans. A 0-10 electricalcontractor,certifiedinfire alarmsystems,mustcertifythe systemis operational annually.(FD) Automatic Fire Sprinklers will be requiredto beequippedwith a fire sprinklersystem. Section17.56.450of the HBMCstatesthat ifa buildingremovesthe entireroofstructureduring the improvementprojectthatsection903of the CFCshallapplyto the project. The aforementionedcodesectionalsostatesthat ifsquarefootageis beingaddedto anyof the buildings,thenfire sprinklerswill also be requiredinthosebuildings. Note: 2002 Brookhurstisrequiredto beequippedwith a fire sprinklersincethe entireroofstructurewill be removedduringthe improvementproject(removalof entiresecondfloorand roofstructure). Also ifthesquarefootageoftheother three buildingsincreases,thensprinklerswill berequiredinthosebuildings. • Page3of 4 Automaticfire sprinklerswill be designedand installedto complywith all NFPA13 standards. Separateplans(twosets)shallbe submittedto the FireDepartmentfor permitsand approval. Fire DepartmentConnections(FDC)to the automaticfire sprinklersystemsshall be locatedin an approvedlocation.(FD) Fire PersonnelAccess Main SecuredBuildingEntriesaccessshallbe provided,utilizinga KNOX®FireDepartment Access KeyBox, installedand in compliancewith CitySpecification#403, FireAccessfor PedestrianorVehicularSecurityGates& Buildings.Theapproximatelocationof the system controlsshallbe notedonthe plans.Referencecomplianceinthe plannotes.(FD) BuildingConstruction The followingitemsshall becompletedpriorto issuanceof a certificateof occupancy. Exit Signsand Exit PathMarkingswill be providedin compliancewith the HuntingtonBeach FireCodeandTitle 24 ofthe CaliforniaAdministrativeCode.Referencecomplianceinthe plan notes.(FD) EgressIllumination/EmergencyExitLightingwith emergencyback-uppoweris required. Providemeansof egressilluminationper HBFC604.2.4and UBC1003.2.9.(FD) Exit Waysand AislesPlan is requiredfor this project.HBFCsection408.2.1.Plansshallbe submittedindicatingthe seatingarrangement,locationandwidth ofexitwaysand aislesfor approvalandan approvedcopyof the planshallbe keptondisplayon the premises.(FD) THEFOLLOWINGCONDITIONSSHALLBE MAINTAINEDDURINGCONSTRUCTION: a.Fire/EmergencyAccessand SiteSafetyshallbe maintainedduringprojectconstructionphasesin compliancewith CFCChapter33, FireSafetyDuringConstructionAnd Demolition.(FD) OTHER: a.OutsideCity Consultants:The FireDepartmentreviewofthis projectandsubsequentplansmay requirethe useof Cityconsultants. The HuntingtonBeachCityCouncilapprovedfee schedule allowsthe FireDepartmentto recoverconsultantfeesfromthe applicant,developeror other responsibleparty.(FD) FireDepartmentCitySpecificationsmaybe obtainedat: HuntingtonBeachFireDepartmentAdministrativeOffice Page4of 4 CityHall2000 MainStreet,5thfloor HuntingtonBeach,CA 92648 orthroughthe City'swebsiteat www.surfcity-hb.org Ifyou haveanyquestions,pleasecontactthe FirePreventionDivisionat (714)536-5411. SAPreventioMl-Development11-PlanningDepartment- PlanningApplications,CUP's12010CUP's\PCH21100 (Hilton HotelExpansion)PA#09- 32108-25-10DM.doc