HomeMy WebLinkAboutOrdinance #3174 ORDINANCE NO. 3174
AN Y THE ORDINANCE F I C O CITY OF HUNTIN T N BEACH G 0 CH
AMENDING CHAPTER 17 . 56 OF THE
HUNTINGTON BEACH MUNICIPAL CODE PERTAINING
TO THE UNIFORM FIRE CODE
WHEREAS, the City Council of the City of Huntington Beach
has adopted the Uniform Fire Code and now wishes to clarify and
update the definition and composition of the Municipal Code as
it relates to the Uniform Fire Code.
NOW, THEREFORE, the City Council of the City of Huntington
Beach does hereby ordain as follows :
SECTION 1. That Chapter 17 . 56 of the Huntington
Beach Municipal Code is hereby repealed and replaced as
follows :
I
Chanter 17.56
t:
UNIFORM FIRE CODE
Sections:
17. 56. 010 Adoption
17. 56 . 015 Definition
17 . 56 . 020 Appeals
17 . 56 . 025 New materials, processes or occupancies--Permits
17 . 56 . 030 Section 3 . 101 amended--Unlawful continuance of a
fire hazard
17 . 56 . 035 Section 4 . 108 amended--Permits
1.7. 56 . 040 Section 9 . 110 amended--ADD High Rise
17. 56 . 045 Section 10 .204 amended--Dimensions for Roadway
Access
17. 56 . 050 Section 10 . 506 amended--Fire Extinguishing Systems
17 . 56 . 055 Section 10 . 507 amended--Automatic Fire
Extinguishing Systems
17. 56 . 060 Section 10 . 509 amended--Permissible Sprinkler H
Omissions
17 . 56 . 065 Section 10 . 510 amended--Standpipes
17 . 56 . 070 Section 11.201 amended--Incinerators
17. 56 . 075 Article 29 amended--Repair Garages
17. 56 . 080 Article 36 amended--Dry Cleaning
17 . 56 . 085 Section 61. 105(c) amended--Location `
i,
AJFk 6/92152 1
17. 56 .090 Section 79 .301 (b) amended--Stationary Tank
Storage-Inside of Buildings
17. 56 . 095 Section 79 . 501 amended--Stationary Tank
Storage-Outside of Buildings
17 . 56 . 100 Section 79 . 601 amended---Tank Storage Underground
17 . 56 . 110 Section 79 . 903(a) (b) (c) amended--Dispensing
17 . 56 . 115 Section 79 . 907 amended--Drainage and Waste
Disposal I;
17 . 56 . 120 Section 79 . 1102 amended--Location
17 . 56 . 125 Section 79 . 1103 amended--Waste Control
17 . 56 . 130 Section 79 . 1104(b) amended--Sumps
17 . 56 . 135 Section 79 . 1112 Add--Huntington Beach Oil Code
17 . 56 . 140 Section 80 . 105 amended--Unauthorized Discharges
17 . 56 . 145 Section 81. 108(a) amended--Aisles
17. 56 . 150 Adopt Appendix I-A amended--Life safety
requirements for existing buildings other than
high rise
17. 56 . 155 Appendix II-C amended--Marinas
17. 56 . 160 Adopt Appendix II-E amended--Hazardous materials
management plan and hazardous materials inventory
statement
17.56.010 Adoption. There is adopted by the City Council, for
the purpose of prescribing regulations governing conditions
hazardous to life and property from fire or explosion, that
certain code and standards known as the Uniform Fire Code,
including Appendices I-A, I--B, I-C, II-A, II--C, II-E, III-A,
III-C, IV-A and VI-A and amendments thereto, published by the
Western Fire Chiefs Association and the International
Conference of Building Officials, being particularly the 1991
edition thereof and the 1991 supplement to the Uniform Fire
Code and the whole thereof, save and except those portions as
are hereinafter modified or amended, of which code and
standards not less than one (1) copy has been and is now filed
in the office of the City Clerk, and the same is hereby adopted
and incorporated as fully as if set out at length herein, and
from the date on which such Uniform Fire Code shall take
effect, the provisions thereof shall be controlling within the
limits of the city of Huntington Beach and shall hereinafter be
referred to in this chapter as the Huntington Beach Fire Code.
17.56.015 Definition. Wherever the word "jurisdiction" is
used in the Huntington Beach Fire code, it shall mean the city
of Huntington Beach.
17.56.020 Appeals. Whenever the Chief of the Fire Department
shall disapprove an application or refuse to grant a permit
applied for, or when it is claimed that provisions of this code
do not apply, or that the true intent and meaning of this code
has been misconstrued or wrongly interpreted, the applicant or
AJFk 6/92152 2
3174
permittee may appeal from the decision of the Chief of the Fire
Department to the Huntington Beach appeals board within thirty
(30) days from the date of the decision appealed.
17.56.025 New materials, processes or occu
pancies--Permits.
The City Administrator, the Chief of the Fire Department, and
the Chief of the Fire Prevention Division shall act as a
committee to determine and specify, after giving affected
persons an opportunity to be heard, any new materials,
processes or occupancies which shall require permits in
. addition to those now enumerated in this code. The Chief of
the Fire Prevention Division shall post such list in a
conspicuous place in his office, and distribute copies to
interested persons .
17.56.030 Section 3.101 amended--Unlawful continuance of a
fire hazard. Section 3 . 101 is amended by hereby adding
subsections (a) , (b) , (c) to read as follows:
(a) Except as provided in Section 3 . 101(b) any person
operating or maintaining any occupancy, premises or vehicle
in violation of this code shall be guilty of an infraction.
(b) Any person who shall fail to take immediate action to
abate a Fire or Life Safety Hazard when ordered or notified
to do so by the Chief or his duly authorized representative
or who violates the following sections of this code or the
Municipal Code shall be guilty of a misdemeanor :
UNIFORM FIRE CODE
3 . 101 Unlawful continuance of a hazard
3 . 102 Compliance with orders and notices
3 . 103 Compliance with condemnation tag
3 . 104 Removal and destruction of signs and tags
10 . 104 Tampering with fire protection equipment and site
barriers
11 . 503 Discard burning objects
13 .302 False alarms
77.301 Use and handling
77 .302 Transportation of explosives
77 .402 Manufacturing of explosives is
is
HUNTINGTON BEACH MUNICIPAL CODE OIL
15 .20 . 120 Wellhead Safety Equipment
15 .20 . 130 Blowout Prevention
15 .24 . 040 Releasing of Fluids
15 .28 . 010 Waste Water System jj
15 .32 . 020 Production Report-Failure
15 .32 . 030 Production Report-False
AJFk 6/92152 3
3174
............
HAZARDOUS MATERIALS
17. 58 . 050 Users of hazardous materials--Disclosure required
(c) Each such violation will be deemed a separate offense
for each and every day or portion thereof during which any
violation of any of the provisions of this chapter or of
the code adopted hereby is committed, continued or
permitted by such person, firm, partnership or corporation,
and shall be deemed punishable therefor as provided in this
chapter.
17.56.035 Section 4.108 Permits.
Delete g . 1
ADD r.3 as follows :
Repair Garages . To use a structure as a place of
business for servicing or repairing motor vehicles . is
See Article 29 .
17.56.040 Section 9 .110 amended--Add HIGH RISE. High-Rise is
any building having floors used for human occupancy located
more than 55 feet above the lowest level of fire department
access . Such buildings shall have fire and life safety systems
required by the Building Code. See UBC Section 1807.
17.56.045 Section 10.204 amended--Dimensions.
(a) Dimensions. Fire apparatus access roads shall have an
unobstructed width of not less than 24 feet and an
obstructed vertical clearance of not less than 13 feet 6
inches. Fire access streets, drives or roads adjacent to
building fronts in commercial centers shall be not less
than 27 feet wide. EXCEPTION: Upon approval by the Fire
Chief, vertical clearance may be reduced, provided such
reduction does not impair access by fire apparatus and
approved signs are installed and maintained indicating the
established vertical clearance.
17.56.050 Section 10.506 amended--Fire Extinguishing Systems
(a) GENERAL. Fire extinguishing systems shall be
installed in accordance with the Fire Code.
(b) STANDARDS. delete exceptions 2 and 3 .
(c) ADD- For the purposes of this code, high-rise
buildings are defined in Section 9 . 110 .
AJFk 6/92152 4
3174
IE
17.56.055 Section 10.507 Amended--Automatic Fire Extinguishing
-Systems
(b) (delete Group R, Division 3)
Whenever the total gross floor area exceeds 5, 000
square feet for all new construction, additions to
existing buildings, or change of occupancy
classification or as required below.
(c) Group A Occupancies. Change subsections 1 and 3; add
subsections 8, 9, 10 as follows :
1. Change 'one hour' to ' four hours ' .
3 . Change 12, 000 to 5,000.
8. ADD- Other areas throughout the building where L
there is a stage or enclosed platform.
9 . ADD- Throughout the building where a portion of
the building above the first floor is used for
drinking and/or dining.
10 . ADD—Throughout the building when a portion of
the building above the first floor is used for
any assembly purpose other than drinking and/or
dining, with an occupant load of 50 or more
persons .
(d) Group B, Division 2 Occupancies. An automatic
sprinkler system shall be installed in retail sales
rooms classified as Group B, Division 2 Occupancies
where the floor area exceeds 5., 000 square feet or in
Group B, Division 2 retail sales occupancies more than
three stories in height . The area of mezzanines shall
be included in determining the areas where sprinklers
are required.
(i) ADD- Group R, Division 3 Occupancies. An automatic
sprinkler system complying with Huntington Beach Fire
Department standards shall be installed when the total
gross floor areas exceeds 5, 000 square feet, or has an
occupied floor over three stories, or is over 30 feet
in height, as determined by Department of Community
Development.
17.56.060 Section 10.509 Permissible Sprinkler omissions.
(f) ADD- When the gross square footage of the building is
divided into nonsprinklered 5, 000 square feet units by
a four hour masonry fire resistive separation walls,
the four hour masonry walls shall have no openings,
shall have parapets 30 inches above the roofline, and
extend horizontally to separate exterior combustible
AJFk 6/92152 5
3174
---------........................
cornices, canopies, etc. EXCEPTION: If four hour
masonry walls are not extended horizontally, a 5 foot
distance shall be provided between the four hour
masonry wall and exterior combustible cornices,
canopies, etc.
I,
17.56,.065 Section 10.510 amended--Standpipes.
Table 10 . 510A:
�s
1 . Standpipes for sprinklered buildings shall be Class
III .
2 . Change 4 stories to 3 stories . Standpipes for
sprinklered buildings shall be Class III .
5 . Change 4 stories to 3 stories; 20,000 square feet per
floor to 10, 000 and standpipes for sprinklered
buildings shall be Class III .
17.56.070 Section. 11.201 amended--Incinerators. Incinerators,
open burning and commercial barbecue pits shall be in
accordance with this Division. The Fire Chief is authorized to
require that any fire be discontinued or extinguished if smoke
or other odors are offensive to occupants of surrounding
properties .
17.56.075 Article 29 amended--Repair Garages.
Scope
Section 29 . 101. Garages used for service or repair of
motor vehicles classified as Group B, Division 1, or Group
H, Division 4 occupancies shall be in accordance with this
article.
Permits
Section 29 . 102 . For permits to use a structure as a
place of business for the purpose of servicing or repairing
motor vehicles, see Section 4 . 108, permit r--3 .
Flammable and Combustible Liquids
Section 29 . 103
(a) General. Storage use, and handling of flammable or
combustible liquids shall be in accordance with applicable
requirements of Article 79 , Divisions I-IX, and this
section.
AJFk 6/92152 6
3174
(b) Dispensing Inside of Building. Class I liquids
shall not be dispensed or transferred within a repair
garage, except as provided in Section 79 . 903 (h) .
When Class II and Class III-A liquids are allowed to
be dispensed in lubrication or service rooms,
electrical and fuel burning equipment shall comply
with Sections 79 . 905 and 79 . 906 .
For operations involving dispensing of fuel into the "
p g P g I€
fuel tanks of motor vehicles, see Article 79, Division j
IX.
(c) Storage and Use in Buildings with Basements or Pits.
When Class I liquids are stored or used within a building
having a basement or pit into which flammable vapors could
travel, the basement or pit shall be provided with
ventilation designed to prevent the accumulation of
flammable vapors therein.
(d) Storage and Handling of Liquids Drained from Vehicles.
1. Motor Vehicle Fuel. Motor vehicle fuel shall not
be drained in Group B, Division I Occupancies .
Liquids drained from motor vehicle fuel tanks in
Group H, Division 4 occupancies shall be stored
and handled as required for Class I liquids in
accordance with Article 79 .
' 2 . Lubricating Oil. Lubricating oil which has
been drained from motor vehicles in Group B,
Division I or Group H, Division 4 occupancies
shall be stored and handled as required for Class
III-B liquids in accordance with Article 79 .
3 . Mixed Liquids. Containers or tanks containing
a mixture of fuel and lubricating oil shall be
installed in accordance with Article 79 for Class
I liquids .
(e) Storage. Liquids stored inside of buildings shall
be kept in containers or tanks complying with Article 79 ,
Division II and III . Liquids stored outside shall be kept
in containers or tanks complying with Article 79, Division
IV or V.
E,
Tank drainage lines terminating inside a building
shall be equipped with a nonremovable-type cap, such as a
hinged cap.
(f) Spill Control. Spill control shall be provided in
accordance with 79 . 115 .
a
AJFk 6/92152 7
3174
(g) Oily Waste Materials. Oily rags and similar
materials shall be stored in metal, metal lined, or other
approved containers equipped with tight-fitting covers .
Sources of Ignition
29.104
(a) General. Devices which generate a spark, flame or
glow capable of igniting gasoline vapors shall not be
within 18" of the floor.
Smoking and open flames shall be prohibited in areas
used for servicing internal combustion engines .
(b) Welding. Welding operation shall be conducted only
in Group H, Division 4 occupancies, and shall be in
accordance with Article 49 .
17.56.080 Article 36 amended--Dry Cleaning.
Scope
Section 36.101. Dry cleaning plants and systems using
only noncombustible liquids and dry cleaning plants that
are not accessible to the public which use flammable and
combustible liquids only for spotting operations shall be
in accordance with this article.
For other dry cleaning operations, see Article 79 , Division
XVII .
Permits
Section 36. 102. For permits to engage in dry cleaning, see
Section 4 . 108 .
Dry Cleaning Equipment
Section 36.103
(a) Compatibility. Equipment used for dry cleaning shall
be compatible with the type of solvent utilized and
shall be installed in accordance with the
manufacturer' s recommendations .
(b) Solvent Handling Systems.
1. Transfer. The transfer and circulation of
solvent shall be through closed systems .
2. Pumps. Pumps used for the transfer or
circulation of solvents shall be designed with
AJFk 6/92152 8
3174
leakproof seals . Positive displacement pumps shall be
fitted with relief valves or bypasses to prevent
I
overpressure. {
I
3 . Physical Protection. Flow and level
sightglasses shall be protected against physical
damage.
4 . Testing. Piping, valves and sightglasses shall
be tested at a minimum of 150 percent of the system' s i
maximum operating pressure. Testing shall be in
accordance with nationally recognized standards. See
Section 2.304(b) , Standard a. 1.5 .
(c) Exhaust Ventilation Systems. Dry cleaning units shall �>
be provided with an automatically activated exhaust 3=
ventilation system to maintain a minimum of 100 feet j
per minute air velocity through the loading door when
the door is opened. Such systems for dry cleaning
equipment shall be in accordance with the Mechanical
Code. See Uniform Mechanical Code Chapter 11.
i
Exception: An external exhaust ventilation
shroud located immediately outside the loading
door may be used provided the air flow is not
less than 100 times the area of the door opening.
(d) Combustion Air. Combustion air for fuel burning
equipment shall be taken from exterior openings that
are located a minimum of 5 feet from exhaust openings
of dry-cleaning equipment.
Storage of Solvent & Waste Solvents
Section 36.104
(a) Flammable and Combustible Solvents. The storage of
flammable and combustible solvents and waste solvents
shall be in accordance with Article 79, Division II .
(b) Noncombustible Solvents. The storage of
noncombustible solvents and waste solvents shall be in
accordance with Article 80, Division III .
I'
Spotting Operations
i
Section 36.105
(a) General. The local application of solvents for the
removal of stains shall be in accordance with this
section, Article 79, Division VIII and Article 80,
Division IV.
AJFk 6/92152 9
3174
(b) Dispensing at Workstations. Dispensing of solvents
shall be from approved containers . The amount of
flammable and combustible liquid solvents at each
workstation shall not exceed one gallon, one pint of
which may be in a plastic container.
17.56.085 Section 61. 105 amended—Location.
(c) Location. The use of listed portable unvented oil
burning heating appliances shall be limited to
supplemental heating in 'M' occupancies .
17.56.090 Section 79.301 amended—Stationary Tank Storage
Inside Buildings.
(b) Where Allowed. Stationary tanks for the storage of
Class I, II, or III-A liquids are allowed only in
industrial plants, chemical plants, distilleries,
motor vehicle fuel dispensing stations, motor vehicles
service or repair garages, processing plants and
refineries wherein rooms or buildings constructed and
separated as required in the Building Code for Group
H, Division 3 Occupancies or fuel storage for
emergency and standby power systems when approved by
the Chief.
.17.56.095 Section 79 .501 amended- Stationary tank storage,
above ground outside of building
s.
is
Restricted Locations. The limits referred to herein
prohibiting the storage of Class I and II liquids in outside,
above ground tanks are hereby established for all commercial
land use districts as defined in the Huntington Beach ordinance
Code.
EXCEPTIONS: is
(a) Bulk plants may exist in M2 industrial districts
only.
(b) Class III liquids may only be stored on
properties with an 0 or 01 suffix.
(c) Class II liquids may be stored temporarily on
construction sites with the approval of the Fire
Chief.
(d) The storage of Class I and Class 11 liquids in
aboveground tanks is prohibited within the City
of Huntington Reach except at locations
classified as Zone M-2 where permitted by a site
plan use permit on property designated as
potentially suitable for the uses permitted under
AJFk 6/92152 10
3174
these zone classifications by the Huntington
Beach Zoning Ordinance as the same may be amended
from time to time and in accordance with Section
79 . 903(a) .
17.56.100 Section 79.601 amended--Tank storage underground.
outside or under buildings.
(a) Location. A flammable or combustible liquid storage
tank may be located underground, outside of or under a
building if such installation meets the requirements
of this section. The tank shall be so located with
respect to existing foundations and support that the
loads carried by the latter cannot be transmitted to
the tank. The distance from any part of a tank
storing liquids to the nearest wall of any basement,
pit, cellar or property line shall be not less than
three (3) feet. A minimum distance of one (1) foot,
shell to shell, shall be maintained between
underground tanks .
The installation of underground combustible/flammable
liquid tanks is hereby prohibited in all residential
districts . The Fire Chief may authorize installation
of underground combustible/flammable liquid tanks in
agricultural districts .
17.56.110 Section 79 .903 amended--Dispensing
(a) Aboveground Tanks. Class I and Class II liquids shall
not be dispensed into the fuel tank of a motor vehicle
from aboveground tanks EXCEPT as follows :
ABOVE GROUND TANK MODEL POLICY
FOR DISPENSING INTO MOTOR VEHICLES
SCOPE: The storage and dispensing of motor
fuels (does not pertain to LPG) into
tanks of motor vehicles from an above
ground tank(s) , specifically for
commercial, and not intended for retail
sales to the general public, use
applications outside of building
approved by the Fire Chief . NOTE:
This exception was developed
specifically for urban applications .
RESTRICTED LOCATIONS: ESTABLISHMENT OF LIMITS OF DISTRICTS
(ZONES) IN WHICH STORAGE OF FLAMMABLE
OR COMBUSTIBLE LIQUIDS IN OUTSIDE ABOVE
GROUND TANKS ARE PROHIBITED.
AJ'Fk 6/92152 11
3174
II
The limits referred to in Section
79 . 501 of the Uniform Fire Code in
which the storage of flammable or
combustible liquids is restricted shall
be as per local code and as approved by
the Fire Chief .
PLANS: Plans shall be submitted and approved
prior to installation for each
application. The plans shall indicate
the method of storage and dispensing
quantities to be stored, distances from
buildings and property lines, access
ways, fire-protection facilities,
barrier protection, diking (secondary
containment) , design and construction
of tanks, supports, seismic design,
tank venting and vapor recovery, wiring
and equipment, electrical controls,
safety rules, - signage and any
additional information and requirements
required by the Fire Chief.
PERMITS: Permits shall be required in accordance
with Section 4 . 101 U.F.C. of the
Uniform Fire Code. In addition, the
storage and dispensing of each
operation shall be reviewed and
permitted annually to assure compliance
...........
with approved plans . Prior to the
issuance of the Fire Department ' s
permit to install, all other applicable
permits shall be obtained, i .e. ;
Building, Planning, Environmental
Health, Air Quality.
LOCATION ON The minimum distance in feet from
PROPERTY property lines, public ways or
significant buildings in which tank(s)
and dispenser(s) can be located are
hereby restricted to the following
guidelines :
Combination System (tank and dispenser)
Tanks to a maximum of 2200 gallons
capacity shall be located 15 feet from
property lines, public ways or
significant buildings .
The aggregate gallonage per site shall
be limited to 2200 gallons .
AJFk 6/92152 12
3174
Quantities greater than 2200 gallons
aggregate shall be approved by the
Chief .
SEPARATION BETWEEN Except for double-bulkheaded
TANKS: compartmentized tanks, the separation
between each tank shall be 1/6 the sum
of adjacent tank diameter but not less
than 3 feet. (See U.F.C. Table
79 . 504(a) )
FIRE AND EXPLOSION The primary tank shall be protected by
PROTECTION: a minimum listed or approved fire
resistive protection of 2-hour rating
and impact resistance as approved by
the Fire Chief . (Impact resistance
Article 9 definition)
DESIGN AND The design, fabrication and
CONSTRUCTION construction of tanks shall be in
OF TANKS AND accordance with Section 79 . 106
EQUIPMENT:
Equipment - All dispensing equipment
and devices shall be of an approved
type and listed by a nationally
recognized testing laboratory as
approved by the Fire Chief for use in
conjunction with Class I and Class II
liquids and shall comply with Section
IX.
MONITORING: Electronic leak detection that complies
with California Code of Regulations
(CCR) Title 23-2634, shall be required
to monitor the interstitial space
between the primary and secondary tank.
All visible exterior surfaces of an
aboveground storage tank, including any
visible horizontal surface directly
beneath the tank, shall be inspected at
least daily by direct viewing. The
inspection schedule shall be
established such that some of the
inspections are conducted when the
liquids are at its highest level .
A written statement of the routine
monitoring procedures shall be
available at the facility and the
record shall include the frequency of
visual inspections, the location(s)
AJFk 6/92152 13
3174
from which observations will be made,
the name(s) and title(s) of the
persons) responsible for performing
the observations and the reporting
format .
Written records shall be maintained on
site for three (3) years .
PRODUCT DISPENSING: Product dispensing hoses shall be
equipped with a listed emergency
breakaway device designed to retain
liquid on both sides of the breakaway
point. The devices shall be located
between the nozzle and the hose line
and the line and the pump, at each end
of the hose. Such devices shall be
installed and maintained in accordance
with manufacturer' s instructions . (See
NFPA (TIA) 30)
DISPENSING: Dispensers shall be equipped with a
permanently attached, approved pumping
device mounted on top of tank,with an
approved hose of an approved length for
filling vehicles, equipment or
containers . Each tank shall have a
pump that is activated/deactivated when
the nozzle is removed and replaced.
(U.F.C. Section 79 . 903(i) )
PIPE, VALVES, FITTINGS: In addition to other requirements
outlined in U.F.C. Section 79 . Division
VII, the following shall be required:
Piping: All piping shall be enclosed
in two-hour fire protection. Pipes
containing liquid are required to be
double contained. This includes the
base of working and emergency vents and
fuel sleeves . Manifold piping to
connect multiple tanks is prohibited.
A fusible link valve, of the type that
upon heat activation the valve will
close preventing fumes from ignition,
shall be required on all openings other
than working and emergency vents. The
valve shall be approved by the Fire
Chief.
A fire extinguisher with a minimum
classification of 2-A, 20 B:C shall be
AJFk 6/92152 14
3174
---------- ..........................................
provided and so located that it will be
not more than 75 feet from any pump,
dispenser or fill pipe opening . (See
U.F.C. Section 79 . 908)
SUPPORTS AND Tanks shall rest on foundations made of
FOUNDATIONS: concrete, masonry, piling or steel .
Tank foundations shall be designed to
minimize the possibility of uneven
settling of the tank and to minimize
corrosion in any part of the tank
resting on the foundations . Steel tank
supports shall be designed to U.L.
Standard 1709 . (See U.F.C. Section
79 . 505 M and (0 )
ANCHORAGE: Design of Supports : The design of the
supporting structure for tanks shall be
in accordance with well established
engineering principles in accordance
with the Building Code.
Tanks shall be so supported as to
prevent the excessive concentration of
loads on the supporting, portion of the
shell . (See U.F.C. Section 79 . 505(d) )
...Locations -Subject to Flooding: Where a
tank is located in an area that may be
subjected to flooding, the applicable
provisions of Appendix II-B apply.
(See U.F.C. Section 79 . 505(e) )
ii
Seismic Design: The tank supports and
connections shall be designed to resist
damage as a result of such shocks in
accordance with the Building Code.
(See U.P.C. Section 79 . 505(f) )
BARRIER PROTECTION: Guard posts or other means shall be
provided to protect exterior storage
tanks from vehicular damage specified
as follows:
1. 71 steel posts, with 3 ' above and
4 'below grade. The post shall be
secured in a one foot square
concrete footing.
2 . The post shall be of 1/2" steel
(schedule 40) 6" in diameter and
concrete filled with cap.
AJFk 6/92152 15
3174
......................
3 . The posts shall be 36" apart on
center.
4 . The backside of the post shall be
a minimum of 3 ` feet from the tank. is
DIKING: The area surrounding a tank or group of
tanks shall be provided with drainage
or shall be diked to prevent accidental
discharge of liquid from endangering
adjacent tanks, adjoining property or
reaching waterways.
Exception: When double containment is
provided within the construction of the
tank, the diking requirements may be
waived by the Fire Chief . (See U.F.C.
Section 79 .507(a) )
VEHICULAR APPROACH A non-absorbant surface sufficiently
PAD: covering the vehicle fueling area is
required as approved by the Fire Chief.
TANK VENTING AND Emergency relief venting shall be in
VAPOR RECOVERY: accordance with U.F.C. Section 79 .509 4
(b) and N.F.P.A. (TIA) 30A. Emergency
relief vents for gasoline primary and
secondary tanks shall have a flame
arrestor as approved by the Fire Chief .
A coaxial breakaway device as approved
by the Fire Chief shall be required on
phase II vapor recovery systems . Vapor
recovery shall be in accordance with
U.F.C. Section 79 .911 and the Air
Quality authority having jurisdiction.
APPROVED WIRING: All installation of electrical wiring
and equipment shall be reasonably safe
to persons and property. For Class I
liquids where electrical wiring and
equipment are installed, evidence that
such wiring and equipment are of the
type approved for use in the hazardous
locations as set forth in Table 79 .905
and that such wiring and equipment have
been installed in accordance with the
Electrical Code will be required. (See
U.F.C. Section 79 . 905)
is
AJFk 6/92152 16
3174
ELECTRICAL CONTROLS: A clearly labeled manually operated
pump master switch shall be provided in li
an approved location, within 75 feet
of, but not nearer than 15 feet to any
dispenser. Where such master switch is
not visible from all dispensers, the
location thereof shall be indicated by
approved signs . Signs identifying the
pump master switch shall be clearly
labeled "EMERGENCY PUMP SHUTOFF" in 41-
high letters with 1/2" strokes .
The master switch on all individual
pump circuit switches shall be set in
the "off" position before close of
business .
SAFETY RULES: There shall be no smoking or open
flames in the areas used for fueling,
servicing internal combustion engines,
receiving or dispensing of Class 1, 11
or III--A liquids . There shall be no
dispensing into unapproved containers .
(See U.F.C. Section 79 .903 (d) )
The motors of all vehicles being fueled
shall be stopped. Conspicuous signs
.. prohibiting. smoking, prohibiting
dispensing into unapproved containers
and requiring vehicle motors to be shut
off during fueling operations shall be
posted at each dispenser.
Flammable or combustible liquids or any
waste liquid containing crude petroleum
or its products shall not be discharged
into or upon any street, highway
drainage canal or ditch, storm drain,
sewer or flood-control channel, lake or
tidal waterway, or upon the ground.
Storage is prohibited on top of the J
tank(s) .
TANK IDENTIFICATION: Above ground storage tanks over 100
gallons (water capacity) permanently
installed, mounted or affixed and used
for the storage of Class I, II or III-A
liquids shall bear the label or placard
in accordance with U.F.C. Standard
Number 79-3 identifying the material
within. A placard shall also be
installed mounted or affixed adjacent
to the "Emergency Shut-off" sign. (See
U.F.C. Section 79 . 110)
AJFk 6/92152 17
3174
J.
TANK FILLING Delivery operations shall comply with
OPERATIONS: applicable requirements of NFPA 385,
Standard for Tank Vehicles for
Flammable and Combustible Liquids .
The delivery vehicle shall be separated i
from any above ground tank by at least I
25 feet (7. 6m) . Tank filling shall not
begin until the delivery operator has
determined tank ullage (available
capacity) . The delivery hoseline shall
not exceed 50 ' .
A dry break coupling shall be installed
at a point where connection and
disconnection is made from the delivery
vehicle to any aboveground tank. This
device shall be protected from
tampering and physical damage. A sign
stating "Do not remove or tamper with
the Dry Break Coupling" shall be
affixed adjacent to the coupling.
is
An overFILL protection system approved
by the Fire Chief is required. The
tank shall be equipped with an
overSPILL box to contain any spill at
the fill opening during delivery
operations, if required by the Fire
Chief. (See NFPA 30A Sections 2 .4 . 8 .2
to 2 .4 . 8 . 5
TESTING: All tank and piping shall be tested , in
a manner acceptable to the
jurisdiction. (See U.F.C. Section !
79 . 708)
FENCING: Fencing shall be provided for all
installations . Fencing shall not be
less than 6 feet in height, constructed ;
of wire mesh, solid metal sheathing or J;k
masonry. Fencing shall be so located
as to provide protection from tampering
or trespassing.
Exception: Tanks are not required to
be enclosed within a fence if the
property on which the tanks are located
already has a perimeter security
fence. (See U.F.C. Section 79 .406)
MAINTENANCE TESTING: The integrity of the primary and
1
secondary h d tanks shall ll be tested
Y ank
AJFk 6/92152 18
3174
annually or after a significant event
or possible breach of integrity, by the
tank owner or operator using the tank
monitoring port. All test results
shall be maintained on the premises for
three (3) years and shall be made
available to the Fire Chief upon
request . (See U.F.C. Sections 79 . 902
(e) and (f) )
The tank integrity tests at a minimum
shall :
1 . Test for vapor in the
interstictial space.
2. Secondary tank - vacuum or
pressure procedure approved by the
Fire chief .
COMMUNICATIONS: During hours of operation, the system's
site - shall be provided with a fire
alarm transmitting device. Such a
device may be a telephone that is
readily available. (See U.F.C. Section
79 . 902(i) (1988) )
SUPERVISION: Where dispensing of Class I, II or
III-A liquids is performed a listed
automatic-closing-type nozzle valve
shall be used incorporating the
following features (See U.F.C. Section
79 . 903) :
1. The hose nozzle valve shall be
equipped with an integral
latch-open device.
2. When the flow of product is
normally controlled by devices or
equipment other than the nozzle
valve, the hose nozzle valve shall
not be capable of being opened
unless the delivery hose is
pressurized. If pressure to the
hose is lost, the nozzle shall
close automatically.
Exception: Vapor recovery nozzles
incorporating Insertion Interlock
devices designed to achieve
shut-off upon disconnection with
vehicle fill pipe.
AjFk 6/92152 19
3174Ir
-----------------------
...........
3 . (a) The hose nozzle shall be
designed in such a way that the
nozzle is retained in the fill
pipe during the filling operation.
(b) Supervision: the dispensing
of Class I and Class II liquids
into a fuel tank of a vehicle or
into a container shall at all
times be under the supervision of
a qualified attendant.
Exception: Supervision by a
qualified attendant is not
required at locations, provided:
1. The owner or operator
provides and is accountable for:
A. At least daily site
visits .
B. Regular equipment
inspection and maintenance.
C. Conspicuously posting
instructions for safe
operation of dispensing
equipment.
D. Posting the phone number
of the owner operator.
2 . A sign in addition to that
required in Section 79 . 903 (d) is
posted in a conspicuous location
stating :
IN CASE OF FIRE OR SPILL
1. Use Emergency pump shut-off
2. Report the accident
FIRE DEPARTMENT #: 911
FACILITIES ADDRESS
3 . Dispensing equipment complies with one
of the following :
A. The amount of fuel being
dispensed is limited in
quantity by a preprogrammed
card set to limit fuel
delivery to 25 gallons and
AJFk 6/92152 20
3174
shall require a manual action
to resume continued delivery,
or
B. Product delivery hoses
are equipped with a listed
emergency breakaway device
designed to retain liquid on
both sides of the breakaway
point. Such double-breakaway
devices shall be installed
and maintained in accordance
with manufacturer ' s
instruction.
79 . 903(b) - Refer to Article 29 .
79 . 903(c) to read as follows :
(c) Portable Containers and Tanks. Class I, II or III-A
liquid shall not be dispensed into portable containers
unless such container is of approved material and
construction, having a tight closure with screwed or
spring cover so designed that the contents can be
dispensed into without spilling. Dispensing into
portable tanks is prohibited.
Class I, II, or III-A liquid shall not be dispensed
into cargo tanks unless the tanks are approved tanks
of 110 gallon aggregate capacity or less and
permanently mounted to the vehicle frame of the motor
vehicle. Cargo tanks with a capacity of over 110
gallons shall be filled at a bulk plant/terminal .
17.56.115 Section 79.907 amended--Drainage and Waste Disposal
Refer to Article 29 .
17.56.120 Section 79 .1102 amended--Location.
(b) Streets and Highways. No oil well shall be drilled
within 25 feet of any dedicated public street, highway
or nearest rail of a railway being used as such.
(c) Buildings. The distances set out in this subsection,
at the discretion of the Chief, may be reduced if :
1. Fire protection system is installed in or on the
structure to meet the standards and specification
of the City of Huntington Beach, and
2 . The proposed structure has a six foot masonry
wall to act as a fire separation.
3 . Or an alternate means of fire protection approved
by the Fire Chief.
AJFk 6/92152 21
3174
f-
i
17.56.125 Section 79.1103 amended--Waste Control.
(b) Discharge and Combustible Materials on Ground. As
follows: The surface of the ground under, around or
near wells, pumps, boilers, oil storage tanks or
buildings shall be kept free of oil, waste oil, refuse
or waste material .
17.56.130 Section 79. 1104 amended_Sumns.
(b) Backfilling Sumps. The maintenance of any sump or
other basin for the retention of oil or petroleum
products in the City is prohibited.
17.56.135 Section 79. 1112 ADD--Huntington Beach Oil Code.
ADD--The Huntington Beach Oil Code (Huntington Beach
Municipal Code Title 15) is incorporated herein by
reference, and declared to be part of the Huntington Beach
Fire Code as though set out in full herein.
E
17.56.140 Section 80. 105--amended Unauthorized Discharges.
(e) Responsibility for Cleanup.
1. lst Clean-Up Criteria. Soils sampled during site
assessments that fail California Assessment Manual
(CAM) criteria for hazardous waste will be excavated
and disposed of at a proper disposal site. Laboratory
tests used in this determination are pH (EPA-9045) ,
CAM Metals (total) , and Volatile Chlorinated and
Aromatic Hydrocarbons (EPA-8240) as described in t
80 . 105(e) 6, Site Assessment and Laboratory !
Specifications .
2 . 2nd Clean-Up Criteria. Comparison of the total
petroleum hydrocarbons (TPH) concentration in soils
sampled during the site assessment shall be made with
the screening criteria in 80 . 105(e) Table 1. If the
sample results meet the Table 1 criteria, no further
testing or remediation work will be required.
If the TPH exceeds the screening criteria, the
laboratory will perform the additional analyses 3
specified (EPA-8020, EPA-8270) . Further delineation
of the contaminated soil through use of additional
borings, additional trenches or by excavation and
stockpiling must be performed to determine the lateral
and vertical extent of soil exceeding Table 1
criteria. Samples obtained during this delineation
will be analyzed for screening criteria listed in
Table 1 (EPA-418 . 1 and EPA-8015) . If sample results
exceed the screening criteria in Table 1, the
AJFk 6/92152 22
3174
5 . On Site Remediation. Soil can be remediated on
site as long as it does not exhibit any
characteristics of material considered hazardous for
2
disposal purposes . On site remediation must comply
with all applicable state, county, federal and city
regulations. Remediation activities shall be
performed within a designated area . A remediation
plan shall be approved by the Fire Department.
After soil is remediated and reused, the surface
. of the designated remediation area shall be tested in
accordance with provisions identified herein above. A
testing plan shall be submitted to the Fire Department
for approval as well as a final report which shall
summarize the remediation efforts and post remediation
test results .
6. Site Assessment and Laboratory Specifications.
Analyses performed during site assessments of oil
fields (other industrial or agricultural uses may
require additional analysis) should include pH
(EPA-9045) , CAM Metals (total only, soluble if total
exceeds 10 times (STLC) , Volatile Hydrocarbons
(EPA-8240) , Total Recoverable Hydrocarbons
(EPA-418 . 1) , Total Fuel Hydrocarbons (EPA-8015) ,
Semi-Volatile Organics (EPA-8270) and Polychlorinated
Biphenyls (EPA 8080) .
Vertical limits of hydrocarbon contamination
shall be assessed. Sampling shall extend to a depth
sufficient to identify at least 5 ' of uncontaminated
soil or to a depth not greater than 5 ' above the water
table in cases where regional groundwater will be
impacted by sampling operations .
If the landowner chooses to clean-up the site
using screening criteria specified in 80. 105(e) Table
2, the laboratory analytical work may specify the
reanalyses of samples exceeding screening criteria
specified in 80. 105(e) Table 1. The shelf life for
the samples must not be exceeded when the reanalyses
are run.
The laboratory contract shall specify use of EPA
Method 3630 as a clean-up procedure prior to soil
analysis for CAPNA' s using EPA-8270 if the 418 . 1
results show greater than 1, 000 ppm.
Samples representative of a specific site should
be obtained consistent with a Phase I historical
review of the site. The sampling frequency will vary
depending on potential for on site contamination.
Sampling should be targeted at identified or suspected
contaminated locations on the site.
AJFk 6/92152 24
3174
.....................
Sampling of areas not suspected to be
contaminated shall be done on a random basis according
to a Sampling Plan which shall be approved by the Fire
Department.
The Sampling Protocol, both in terms of site
specific targets and other random sampling should be
formulated in cooperation with the Fire Department .
The burden of demonstrating soil cleanup to
established limits of contamination shall be the
responsibility of the land owner. The Fire
Department ' s approval of a Sampling Protocol shall be
required.
A Site Auditor, as identified in 80 . 105(e) , 8
shall be a requirement placed on all significantly
large oil field properties and on smaller properties
where a reasonable large number of contamination
sources are deemed to remain unsampled following
completion of the approved Sampling Protocol . The
requirement for a Site Auditor shall be at the
discretion of the Fire Department.
Soil sampling shall be carried out using
protocols approved by the California Leaking
. Underground Fuel Tank Manual and/or the Orange County
Healti- Department .
Analytical results which may be inconsistent or
anom-: 73us when compared to other sample data taken as
part of the site assessment shall be made a part of
the record although the land owner shall have the
option of providing additional samples to clarify
inconsistencies . The number and location of these
samples shall be determined by the land owner.
7. Specifications for Reuse of Crude oil
Contaminated Soils as Road Subgrade. Soils must meet
criteria listed in 80 . 105(e) Table 1 and 2.
Reused soils must meet compaction requirements .
Reused soils shall be placed directly beneath the
asphalt cap and underlying aggregate to a maximum
depth of four (4) feet below the road surface. Fills
deeper than four (4) feet must be approved by the Fire
Department based on sufficient findings .
Potable drinking water lines must be surrounded
by clean sand or gravel and approved and inspected by
the appropriate City departments before burial in the
roadway.
AJFk 6/92152 25
3174
A detailed set ' of drawings must be submitted to
the City showing the plan of reused soils, a cross
section of the road base, locations of utility lines
and thickness of clean sand and gravel pack placed
around these lines . Soil analysis data for the road
fill must also be submitted which shall verify
compliance with the standards listed in Table I and/or
Table 2 .
8 . Scope of Contract Specifications for on Site
Auditing During Grading Activities. The Auditor shall
be an independent environmental or geotechnical
consulting company with adequate training to identify
petroleum contaminated soils with field instruments
. and techniques described below. The Auditor shall be
licensed by the State of California as a Registered
Environmental Assessor.
Auditors will monitor grading activities for
indicators that petroleum hydrocarbons may have k
contaminated the soils and shall be aware of the
situations and procedures:
1) Soft spongy soils that become evident as
heavy equipment travels over it .
2) Hydrocarbon odors emanating from the soil .
3) A reading of greater than 20 ppm on a hand
held organic vapor monitor (OVM) held three (3)
inches from suspected contaminated soils . The
meter shall be calibrated at least twice per day.
4) A small vial of solvent can be used to
extract a small amount of soil. If the solvent
becomes discolored petroleum may be present.
If any of the indicators above are found, the
Auditor shall devise a sampling program capable of
ascertaining whether or not waste is classified as
hazardous . All sampling procedures shall be in
accordance with the protocols established by LUTF
and/or the Orange County Health Department . The
contamination citing shall be made a part of the
record and the Fire. Department shall be immediately
notified. k
Sufficient samples shall be analyzed to
characterize the vertical and horizontal extent of the
potential contaminant . If samples exceed the
screening criteria in 80. 105(e) Table 1, the soil must
either be removed or reanalyzed and compared to
criteria in 80 . 105(e) Table 2 . If the soil is
AJFk 6/92152 26
3174
............. . .....
determined to meet the Table 2, criteria, the soil can
be incorporated into the fill. If it does not, the
soil can be stockpiled for remediation and reuse or
removed from the site.
kl
A report documenting the observations made and
samples obtained during grading shall be prepared.
This report shall document compliance with the fs
appropriate sections of Table 1 and/or Table 2, as
applicable.
Section 80.105(e)
Table I
Screening Level for Hydrocarbon Clean-up ` L'.
Residential and Recreational <500 ppm <500 ppm.
Commercial and Industrial <1,000 PPM <1,000 ppm
Roadway
1.
• 0'-4'Below Road Surface n1a <1'O00 ppm.total;
<100 ppm of the <C14 component
>4'Below Road Surface <1,000 PPM <1,0130 ppm,
Section 80.105(e)
Table 2
Screening Leviels for Hydrocarbon Clean-up
211;
-up
Residential and Recreational JB,<1.0 ppm. Each CAPKA <0.5 ppm.
T - PP:m
X&E <10.0 PPM individually Total CAPWs <3.0 ppm
Commercial and Industrial B <1.0 ppm Fach CAPNA<1.0 ppm
X&E <10.0 ppm individually Total CAPNA's <6.0 ppm
Roadway
* 01-4 Below Road Surface B <1.0 ppm EaA CAPKA<1.0 ppm
T,X&E <10.0 ppm individually Total CAl <9.0 ppm
* >V Below Road Surface B <1.0 PPM Each CAPKA <1.0 PPM
T,X&E<10.0 ppm individually Total CAPKA's <6.0 ppm
Based on CAPNVs found In Proposition 65 list,in addition to ba zo(g h&aylene.
27
AJFk 6/92152
3174
17.56. 145 Section 81.108--amended Aisles. Section 81 . 108 is
hereby amended by adding subsection (a)4 to read as follows :
(a) Aisles
4 . shall comply with the requirements for exits and
the following :
1. When mechanical stocking methods are
utilized, the minimum aisle width shall be
eight (8) feet .
2 . When manual stocking methods are utilized,
the minimum aisle width shall be forty-four
(44) inches
3 . During the stocking operation, a minimum
exit width of forty-four (44) inches shall
be maintained.
4 . When cross aisles are provided the maximum
required width shall be fourteen (14) feet.
5. Aisles shall not have a dead end greater
than twenty (20) feet in length.
17.56.150 Adopt Appendix I-A amended--Life safety requirements
for existing buildings other than high rise.
1. GENERAL.
(a) Purpose.
EXCEPTION: Group R, Division I less than seven
(7) units, Group R, Division 3; Group M; and high rise
occupancies .
2 . EXITS.
(b) Corridors .
EXCEPTION: Existing corridor walls, ceilings,
and protection for openings not in compliance with the
above may be permitted when such buildings are
equipped with an approved automatic sprinkler system
throughout to comply with the standards and
specifications of the Huntington Beach Fire
Department.
AJFk 6/92152 28
3174
-----------
17.56. 155 Appendix II-C amended---Marinas.
2 . GENERAL.
Plans for marina fire-protection facilities shall be
approved by the Chief prior to installation. The completed
work shall be subject to final inspection and approval
after installation. Two (2) sets of plans shall be
submitted to the Fire Department indicating :
(a) The dock layout.
(b) The location of wet standpipe outlets,
accompanied by pipe schedules and hydraulic
calculations.
(c) Location of fire extinguisher cabinets .
6 . FIRE-PROTECTION EQUIPMENT.
All piers, wharves, floats with facilities for mooring
or servicing five (5) or more vessels, and marine service
stations shall be equipped with fire protection equipment
as follows :
(a) A wet standpipe system shall be installed on all
docks, piers, wharves, or marine service stations that
exceed one hundred (100) feet in length or are
otherwise inaccessible from City fire hydrants . The
wet standpipe system shall be capable of delivering
two-hundred and fifty (250) gallons per minute at a
residual pressure of fifty (50) psi at the outlet.
The outlet shall be a two-and-one-half (2 1/2) inch
national standard thread with an approved gate valve.
Outlets shall be spaced at two hundred (200) foot
intervals, in approved locations, preferably at point
of public access. Outlets shall be installed so that
they are readily visible, unobstructed and readily
discernible as a piece of firefighting equipment .
(b) Piers and wharves shall be provided with fire
apparatus access roads and water supply systems with
on-site fire hydrants as may be required by the
Chief . Such roads and water systems shall conform to
Article 10 of this code.
(c) The wet standpipe system shall be provided with a Fire
Department siamese connection which shall be located
within five (5) feet of the nearest fire apparatus
access roadway.
AJFk 6/92152 29
3174
(d) PORTABLE FIRE-PROTECTION EQUIPMENT.
(1) A 4A, 40-B:C fire extinguisher shall be located
every one hundred and fifty (150) feet along the
dock. The fire extinguisher shall be located in
a standard fire extinguisher cabinet with a
breakable glass front. The cabinet shall have
placards on both sides with the words ' FIRE
EXTINGUISHER' and either have an additional
placard on the front or shall be easily
recognized from the front as a fire extinguisher
cabinet.
(2) The Chief shall designate the type and number of
all other fire appliances to be installed and
maintained - in each marina.
7. TRANSMISSION OF ALARMS.
A means for transmitting alarms immediately to the
Fire Department shall be available pursuant to the
standards and specifications of the Huntington Beach Fire
Department.
17.56.160 Adopt AP
pendix II-E amended--Hazardous Materials
Management Plan and Hazardous Materials Inventory Statement.
1 . SCOPE
ADD--The Huntington Beach Municipal Code, Chapter
17.58 is incorporated herein by reference, and declared to
be part of the Huntington Beach Fire Code as though set out .
in full herein. The intent of Appendix II-E and Municipal
Code Chapter 17. 58 is deemed to be substantially equivalent
in intent .
SECTION 2. This ordinance shall take effect thirty
(30) days after its passage.
PASSED AND ADOPTED by the City Council of the City of
Huntington Beach at a regular meeting thereof held on the 7th
day of December
1992.
Mayor
ATTFST: APPROVED S APPROV T0 ,7ORM:
City Clerk //-/P�-eity Attorney
P PPROVE
PROVE INITIATE AND APPROVED:
rator
6 rator Fire Chief
AJFk 6/92152 30
3174
DOCUMENTATION
is
THE UNIFORM FIRE CODE SECTIONS REFERENCED
IN THIS DOCUMENT ARE BASED UPON THE 1991 EDITION
FINDINGS
1. THIS STANDARD PROVIDES A REASONABLE DEGREE OF FIRE
PROTECTION.
2. IT IS CONSISTENT WITH SECTION 2 . 301 AND 79 . 101 (C)
CONCERNING ALTERNATE MATERIALS OR METHODS AND AFTER
CONSIDERATIONS OF SPECIAL FEATURES IN THE PROXIMITY TO
BUILDINGS OR ADJOINING PROPERTY, CHARACTER, CONSTRUCTION OF
EQUIPMENT AND DEGREE OF FIRE PROTECTION.
is
THEREFORE, I, THE FIRE CHIEF OF THE CITY OF HUNTINGTON BEACH,
DECLARE THAT THE ABOVE USE AND PRACTICES, WHEN INSTALLED AND
MAINTAINED IN ACCORDANCE WITH THIS STANDARD, MEETS THE INTENT
OF SECTION 1 . 102(A) OF THE UNIFORM FIRE CODE WHICH IS TO
PROVIDE A REASONABLE DEGREE OF FIRE SAFETY.
Michael Fire Chief Date
AJFk 6/92152 31
3174
r y Ord. No. 3174
STATE OF CALIFORNIA )
COUNTY OF OF HUNT RANGE ss
CITY I GTON BEACH �
I, CONNI£ BROCKWAY, the duly elected, qualified City
Clerk of the City of Huntington Beach and ex-officio Clerk of the
City Council of the said City, do hereby certify that the whole number
of members of the City Council of the City of Huntington Beach is seven;
that the foregoing ordinance was read to said City Council at a regular
meeting therof held on the 16th day of November
and was again read to said City Council at a regular__ __
meeting therof held on the 7th day of December 19 92 , and
was passed and adopted by the affirmative vote of at least a majority of
all the members of said City Council ,
AYES: Councilmembers:
ROBITAILLE, MOULTON-PATTERSON, WINCHELL, SILVA, SULLIVAN, LEIPZIG
NOES: Councilmembers:
NONE
ABSENT: Councilmembers:
NONE
I, Connie Brcftay CITY CLERK of tha Ci!y of y}�
Hu3'lfina!on W^"Ch r,,Td ex cffll,!o of:if''. ily • rid+ ram' I
CeE.. ,«,
ton City Clerk and ex-offi ci o Clerk
of the City Council of the City
j of Huntington Beach, California
e.. _,.._,...`..... City Cork
1 L� c1 `61 Deputy City C�"!c