HomeMy WebLinkAboutOrdinance #3571 ORDINANCE NO. 3571
AN ORDINANCE OF THE CITY OF HUNTINGTON BEACH
AMENDING HUNTINGTON BEACH MUNICIPAL CODE
CHAPTER 17.56 ADOPTING THE CALIFORNIA FIRE CODE
WHEREAS, Section 17958.5 of the California Health and Safety Code permits the City
to make changes or modifications to the California Fire Code as such changes or modifications
are reasonably necessary because of local climatic, geographic or topographical conditions; and
WHEREAS, the Fire Chief of the City of Huntington Beach has recommended that the
California Fire Code be adopted by the City with certain changes or modifications which are
necessary to meet local climatic, geographical or topographical conditions.
The City Council of the City of Huntington Beach does hereby ordain as follows:
SECTION 1. Findings. The following findings are hereby adopted in support of
Chapter 17.56 and the amendments thereto. The findings shall not be codified.
FINDINGS
The City of Huntington Beach is aware that due to the following climatic, geological and
topographical conditions there is potential for disasters and major fires.
Climatic Conditions
The City of Huntington Beach is located in a semi-arid costal plain. It experiences
periods of moderate temperatures with little or no precipitation and periods of storm activity with
associated rainfall.
Hot, dry, high velocity winds (called Santa Ana winds) are common in the area. These
winds reduce the relative humidity causing severe drying of the vegetation and common building
materials. These dry conditions predispose the area to large destructive fires (conflagration).
The local climate is currently in a drought condition. Dry climatic conditions can create
the potential for the rapid spread of fire in both vegetation and structures. The addition of fire
protection systems will supplement the Fire Department response by providing immediate
protection for the building occupants and by containing or controlling the spread of fire. Fire
sprinkler systems also provide an efficient use of water for the control and containment of fires.
The southern boundary of the City is along the Pacific Ocean. Winter storms and tropical
storms come into the City from the ocean. These storms can create high winds and large ocean
waves, which can cause flooding in large areas of the city. Along part of the eastern boundary of
02ordlchapI7-55fire/g/16102 1
Ord.No.3571
the city is the Santa Ana River. This river originates in the San Bernardino Mountains and flows
through many communities until it terminates.in the ocean at the Huntington Beach/Newport
Beach border. The river is contained in a man-made channel. Heavy rainfall and urban runoff
has potential to cause flooding in the flood plain due to the river and/or its tributaries.
Geological Conditions
The City of Huntington Beach is Iocated in an area of high seismic activity. The
Newport-Inglewood Fault runs through the City, which fault is the largest of several faults.
Studies reveal that this fault has the probability of generating a 6.6 magnitude earthquake.
Because of the population density and the number of structures in the City, the risk of life loss
and property damage due to earthquake activity is considerable.
Major earthquakes are always accompanied by the disruption of traffic flow. Fires
caused by damaged flammable gas piping, ruptured fuel storage tanks and electrical arching are
probable. The Fire Department responses to fires and other emergencies may be compromised.
The presence of built-in fire protection systems, and regulation of tank installations provide an
added degree of protection for the community.
The City is located in a low to moderate tsunamis area. These seismic sea waves have
the ability to flood large sections of the low-lying areas. These flood conditions also impact the
response and activity level of the Fire Department.
Topographical Conditions
The City has a population of 195,000 people in 29 square miles. The daytime population
increases significantly in the summer due to beach related activities. Heavy traffic is common on
the City streets and roadways. There are two state highways (Beach Boulevard and Pacific Coast
Highway) and a major freeway (I-405) routed through the City. There are also narrow alleys and
numerous cul-de-sacs present. The ability for fire apparatus access is critical for timely
emergency response. The regulation of these access routes is necessary to help provide
reasonable response times.
The following modifications to the Huntington Beach Fire Code, specifically affect the
California Fire Code and are required due to local climatic, geological and topographical
conditions within the City of Huntington Beach:
A. Section 17.56.040 of the Huntington Beach Municipal Code:
1. The City is in a high seismic hazard zone subject to earthquakes of a significant
magnitude to produce major damage.
2. This amendment would require an increased level of fire and life safety systems
in buildings meeting the definition. An earthquake has the potential to impact fire
02ord/chapI7-55fire/8I15102 2
Ord.No.3571
department response time. The increased level of built in protection may reduce
the impact of increased response times on life safety.
B. Sections 17.56.055, 17.56.060 and 17.56.065 of the Huntington Beach Municipal Code:
1. The City is in a high seismic.hazard zone..
2. Much of the City is in a historical flood plain.
3. Any of the above conditions can effect fire department response times. The
increased sprinkler and fire protection system requirements are to increase the
level of life safety in these buildings.
C. Sections 17.56.075 and 17.56.080 of the Huntington Beach Municipal Code:
1. Much of the City is located in a historical flood plain.
2. The City is in a high seismic area.
3. Many areas of the City contain soils that are corrosive.
4. Many areas of the City contain soils that are expansive when subjected to
excessive moisture.
5. Providing proper size, installation, separation and protection of tanks and
associated components will minimize the risks of deterioration and damage to the
storage tanks and associated piping, valves, fittings and wiring.
6. Pacific storms that create flooding will have a major adverse effect on both
aboveground and belowground tanks.
D. Section 17.56.105 of the Huntington Beach Municipal Code:
I. Many areas of the city contain soils that are corrosive.
2. New tank linings will not remedy the external corrosion of the storage tanks due
to the corrosive soils.
SECTION 2. Section 17.56 of the Huntington Beach Municipal Code is hereby repealed
in its entirety and replaced as follows:
Chapter 17.56
HUNTINGTON BEACH FIRE CODE
Sections:
17.56.010 Adoption
17.56.015 Definition
17.56.020 CFC Section 103.1.4 Amended Appeals
17.56.025 CFC Section 105 New materials,processes or occupancies Permits
17.56.030 Repealed Ord. 3430-7/99
17.56.035 Repealed Ord. 3317-1/96
02ord/chapl 7-55fire/8115/02 3
Ord.No.3571
17.56.040 CFC Section 209-H Amended ADD HIGH RISE
17.56.042 ADD AMENDMENT to CFC Section 902.2, 902.2.1 Required access
17-56.047 ADD AMENDMENT to CFC Section 902.2.4.1 General
17.56.045 CFC Section 902.2.2.1 Amended Fire Apparatus Access Dimensions
17.56.046 CFC Section 902.4 Amended Key Boxes/Gates
17.56.050-CFC Section 1003 Amended Fire Extinguishing Systems
17,56.055 CFC Section 1003.2.2 Automatic Fire Extinguishing Systems
17.56.060 CFC Section 1003.4 Permissible Sprinkler Omissions
17.56.065 CFC Section 1004 Amended Standpipes TABLE 1004-A
17.56.067 ADD AMENDMENT to CFC Section 5102.2.2.1 Semiconductor Fabrication
Facilities-Storage`Aggregate Quantities
17-56.068 ADD AMENDMENT to CFC Section 5103.2.2.1 Semiconductor Fabrication
Facilities-Use and Handling-Aggregate Quantities
17.56.070 Repealed Ord. 3317-1/96
17.56.075 CFC Section 5202.4.1 Amended Aboveground Fuel Tanks
17.56.080 CFC Section 5202.4.5 Dispensing Supervision
17.56.085 CFC Section 6106.3 Portable Unvented Oil-Burning Heating Appliances
17.56.086 ADD AMENDMENT to CFC Section 7503.1.3.7 Testing
17.56.087 CFC Section 7901.3.2 Hazardous Materials Storage Plan
17.56.089 Repealed Ord. 3430-7/99
17.56.090 Repealed Ord. 3317-1/96
17.56.091 Repealed Ord. 3430-7/99
17.56.095 CFC Section 7902.2.2.1 Locations Where Aboveground Tanks Are Prohibited
17.56.100 CFC Section 7902.6.3 Location of Underground Fuel Tanks
17.56.105 CFC Section 7902.6.10 Tank Lining
17.56.110 CFC Section 7903.2.1.4 Heating, Cooking, and Lighting Devices
17,56.115 CFC Section 7903.2.3.4 Mechanical Ventilation
17.56.120 CFC Section 7904.3.2.3 Oil Well Drilling and Operation
17.56.125 Repealed Ord. 3317-1/96
17.56.130 CFC Section 7904.3.4.2 Amended Sumps
17.56.135 CFC Section 7904.3.10 Huntington Beach Oil Code
17.56.140 CFC Section 8001.3.2 Hazardous Materials Management Plan
17.56.145 CFC Section 8001.3.3 Amended Hazardous Materials Inventory Statement
17.56.150 Repealed Ord. 3430-7/99
17.56.155 CFC Section 8001.5.2.2 Notification
17.56.160 Repealed Ord. 3430-7/99
17.56.165.CFC Section 80015.2.5 Responsibility For Cleanup (Soil Spec.)
17.56.170 CFC Section 8001.7 Identification Signs
17-56,175 CFC Section 8001.11.00 Spill Control, Drainage Control, and Secondary
Containment
17-56.180 CFC Section 8001.15.1 Exempt amounts
17.56.182 CFC Section 8003.1.2 Hazardous Materials Signs
17.56.184 CFC Section 8003.1.5 Maximum Quantity Hazardous Materials On Site
17.56.185 Repealed Ord. 3430-7/99
17,56.190 CFC Section 8004.1.1 Applicability
17.56.192 UFC Section 8004.1.9 Hazardous Materials Signs
02ord/chap 17-5 5fire18!3 5102 4
Ord.No.3671
17.56.195 CFC Section 8102.10.2 High Piled Stock Aisle Width
17.56.200 CFC Appendix Life safety requirements for existing buildings other than high rise
17.56.205 CFC Appendix IIC Marinas
17.56.210 CFC Appendix IIE Hazardous Materials Management Plan and Hazardous
Materials Inventory Statement
17.56.220 CFC Appendix II-K Aboveground Tanks
17.56.010 Adoption. There is adopted by the City Council, for the purpose of prescribing
regulations governing conditions hazardous to life and property from fire or explosion, that
certain code and standards known as the California Fire Code, including Appendices I-A, I-B, I-
C, II-A, II-C, 11-D, II-E, II-K, II-H, II-J, III-A, III-C, and IV-A and amendments thereto,
published by Western Fire Chiefs Association and the California Building Standards
Commission,being particularly the 2001 edition thereof(hereinafter CFC) and the Uniform Fire
Code, 2000 edition, save and except those portions as are hereinafter modified or amended, of
which code and standards not less than one (1) copy has been and is now filed in the Office of
the City Clerk, and the same is hereby adopted and incorporated-as fully as if set out at length
herein, and from the date on which such CFC shall take effect, the provisions thereof shall be
controlling within the limits of the City of Huntington Beach and shall hereinafter be referred to
in this chapter as the Huntington Beach Fire Code.
17.56.015 Definition. Wherever the word "jurisdiction" is used in the Huntington Beach Fire
Code, it shall mean the City of Huntington Beach.
17-56.020 UFC Section 103.1.4.Amended Appeals. Any appeal from the decision of the chief of
the Fire Department to the Huntington Beach Appeals Board must be filed within thirty (30)
days from the date of the decision appealed. There shall be no appeal pursuant to this section to
determine the validity of a decision of the fire chief, or his or her designee. pursuant to CFC
Section 103.4.4 or CFC Section 8001.5.2.5.
17.56.025 New materials, processes or occupancies Permits. The City Administrator, the chief of
the Fire Department, and the chief of the Fire Prevention Division shall act as a committee to
determine and specify, after giving affected persons an opportunity to be heard, any new
materials, processes or occupancies which shall require permits in addition to those now
enumerated in this code. The chief of the Fire Prevention Division shall post such list in a
conspicuous place in his office, and distribute copies to interested persons.
17-56.040 CFC Section 209-H Him. High Rise is any building having floors used for
human occupancy located more than 55 feet above the lowest level of Fire Department access.
Such buildings shall have fire and life safety systems required by the Building Code.
17.56.042 CFC Section 902.2.1 Amended Fire A aratus Access. All private streets and
accessways into or within the jurisdiction are hereby designated as fire department access roads.
Fire Apparatus access roads shall be provided in accordance with sections 901 and 902.2 for
every residential, commercial and industrial development, facility, building or portion of a
building hereafter constructed or moved into within the jurisdiction when any portion of the
development, facility building or any portion of an exterior wall of the first story of the building
is located more than 150 feet (45 720 MM) from the fire apparatus access as measured by an
02ord/chapl 7-55fire18/19/02 5
Ord.No.3571
approved route around the exterior of the development, facility or building. Also see Section
902.3 for personnel access to the building.
17.56,045 CFC Section 902.2.2.1 Fire Apparatus Access Dimensions.
(a) Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than
twenty-four (24') feet(7315 mm) and an obstructed vertical clearance of not less than thirteen
(13) feet six (6") inches (4115 mm). Fire access streets, drives or roads adjacent to building
fronts in commercial centers shall be not less than twenty-seven (27') (8230 mm) feet wide.
EXCEPTION: Upon approval by the fire chief, vertical clearance may be reduced, provided such
reduction does not impair access by fire apparatus and approved signs are installed and
maintained indicating the established vertical clearance.
17.56.046 CFC Section 902.4 Key Boxes/Gates. When access to or within a structure or an area
is unduly difficult because of secured openings or where immediate access is necessary for life-
saving or firefighting purposes, the fire chief is authorized to require a key box to be installed in
an accessible location. The key box shall be of a type approved by the chief and shall contain
keys to gain necessary access as required by the fire chief. On all electric vehicle gates leading to
required fire department access lanes, an approved fire department key switch and an approved
strobe light receiver (residential developments only-refer to City Specification#403) shall be
installed and tested by the fire department. In the event of a power failure, the gate shall be
automatically transferred to a fail safe mode allowing the gate to be pushed open without the use
of special knowledge or any equipment.
17.56.047 CFC Section 902.2.4.1, Amended: Fire Apparatus Access Roads-Obstruction. The
required width, surface and construction of a fire apparatus access road shall not be obstructed or
modified in any manner, including the parking of vehicles without the prior approval of the Fire
Chief. Minimum required widths and clearances established under Section 902.2.2.1 as amended
by HBMC 17.56.045 shall be maintained at all times.
17.56.050 CFC Section 1003, Fire Extinguishing Systems.
1003.1.1 General. Fire extinguishing systems shall be installed in accordance with the Fire Code,
and National Fire Protection Association Pamphlet#13.
1003.1.2 Standards. delete exceptions 2 and 3.
ADDFor the purposes of this code, highrise buildings are defined in UFC § 209H.
17.56.055 CFC Section 1003.2.2 Automatic Fire Extinguishing Systems.
1003.2.2 All Occupancies: All Occupancies Except group U occupancies. (For group U
occupancies, refer to City Specification#404). An automatic sprinkler system shall be installed
whenever the total gross floor area exceeds 5,000 square feet for all new construction, additions
to existing buildings {refer to City Specification 9420), or change of occupancy classification to
an assembly, educational, institutional, hazardous or residential use, and as follows:
02ord/chap17-55fire/8/15/02 6
Ord.No.3571
1003.2.3.1 Drinking Establishments:
Line 5 Change '(1) hour'to '(4) hour'.
Line 6 Change one (1) hour to four(4) hour.
1003.2.3.3 Exhibition and Display rooms:
Line 2 Change 12,000 to 5,000.
1003.2.3.7 Stages. All buildings shall be sprinklered, where there is a stage or enclosed platform.
1003.2.3.9 ADD Automatic sprinklers shall be required throughout the building where a portion
of the building above the first floor is used for drinking and/or dining.
1003.2.3.10 ADD Automatic sprinklers shall be required throughout the building when a portion
of the building above the first floor is used for any assembly purpose other than drinking and/or
dining, with an occupant load of fifty (50) or more persons.
1003.2.4.1 General. Delete Exceptions one (1) and two (2).
1003.2.8 Group M Occupancies. An automatic sprinkler system shall be installed in retail sales
rooms classified as Group M Occupancies where the floor area exceeds 5,000 square feet or in
Group M retail sales occupancies more than three stories in height. The area of mezzanines shall
be included in determining the areas where sprinklers are required.
17.56.060 CFC Section 1003.4 Permissible Sprinkler Omissions.
ADD 6. When the gross square footage of the building is divided into nonsprinklered 5,000
square feet units by four hour masonry fire resistive separation walls, the four hour masonry
walls shall have no openings, shall have parapets 30 inches above the roofline, and extend
horizontally to separate exterior combustible cornices, canopies, etc. EXCEPTION: If four hour
masonry walls are not extended horizontally, a 5 foot distance shall be provided between the four
hour masonry wall and exterior combustible cornices, canopies, etc.
17.56.065 CFC Section 1004 Standpipes TABLE 1004A.
Table 1004-A:
Line 1. Standpipes for sprinklered buildings shall be Class III.
Line 2. Change four(4) stories to three (3) stories. Standpipes for sprinklered buildings shall be
Class III.
Line 5. Change four(4) stories to three (3) stories; 20,000 square feet per floor to 10,000 and
standpipes for sprinklered buildings shall be Class III.
02ord/chap 17-55 fire/8/15/02 7
Ord.No.3571
17.56.067 CFC Section 5102.2.2.1 Amended: Semiconductor Fabrication Facilities-Storage-
Aggregate Quantities. The aggregate quantities of hazardous materials stored and used in a single
fabrication area shall not exceed the quantities set forth in Table 5102-A.
17.56.068 CFC Section 5103.2.2.1 Amended: Semiconductor Fabrication Facilities-Use and
Handling-Aggregate Quantities. The aggregate quantities of hazardous materials in a single
fabrication area shall be in accordance with.Section 5102.2.2. See Table 5102-A.
17.56.075 CFC Section 5202.4.1 Amended Aboveground Fuel Tanks. Aboveground Tanks.
Class I and Class 11 flammable liquids shall not be dispensed into the fuel tank of a motor vehicle
from aboveground tanks EXCEPT as follows:
Above Ground Tank Model Policy For Dispensing Into Motor Vehicles
SCOPE:
When approved by the fire chief, the outside storage and dispensing of motor fuels (does not
pertain to LPG) into tanks of motor vehicles from an aboveground tank(s), used in commercial
applications which are not intended for retail sales to the general public.
RESTRICTED LOCATIONS:
ESTABLISHMENT OF.LIMITS OF DISTRICTS (ZONES) IN WHICH STORAGE OF
FLAMMABLE OR COMBUSTIBLE LIQUIDS IN OUTSIDE ABOVEGROUND TANKS
ARE PROHIBITED.
The limits referred to in Section 7902.2.2 of the CFC, as adopted by Huntington Beach
Municipal Code 17.56.095 in which the storage of flammable or combustible liquids is restricted
shall be as per local code and as approved by the fire chief.
PLANS:
Plans shall be submitted and approved prior to installation for each application. The plans shall
indicate the method of storage and dispensing quantities to be stored, distances from buildings
and property lines, accessways, fire protection facilities, barrier protection, diking (secondary
containment), design and construction of tanks, supports, seismic design, tank venting and vapor
recovery, wiring and equipment, electrical controls, safety rules, signage and any additional
information and requirements required by the fire chief.
PERMITS :
Permits shall be required in accordance with Section 105 of the CFC. In addition, the storage and
dispensing of each operation shall be reviewed and permitted annually to assure compliance with
approved plans. Prior to the issuance of the Fire Department's permit to install, all other
applicable permits shall be obtained, i.e., Building, Planning, Environmental Health, Air Quality.
PERMITTABLE LOCATIONS ON PROPERTY:
02ord/chap 17-55 fire18115102 8
Ord.No.3571
The minimum distance in feet from property lines,public ways or significant buildings in which
tank(s) and dispenser(s) can be located are hereby restricted to the following guidelines:
Tanks to a maximum of 2200 gallons capacity shall be located fifteen (15') feet from property
lines, public ways or significant buildings.
The aggregate gallonage per site shall be limited to 2200 gallons.
Quantities greater than 2200 gallons aggregate shall be approved by the fire chief.
SEPARATION BETWEEN TANKS:
Except for double-bulkheaded compartmentalized tanks, the separation between each tank shall
be 116 the sum of adjacent tank diameter but not less than three (3) feet. (See CFC Table 7902.2-
G).
FIRE AND EXPLOSION PROTECTION:
The primary tank shall be protected by a minimum listed or approved fire resistive protection of
2-hour rating and impact resistance as approved by the fire chief. (Impact resistance Article 2
definition.)
DESIGN AND CONSTRUCTION OF TANKS AND EQUIPMENT:
The design, fabrication and construction of tanks shall be in accordance with CFC Section
7902.1.8.1.1.
Equipment All dispensing equipment and devices shall be of an approved type and listed by a
nationally recognized testing laboratory as approved by the Fire Chief for use in conjunction
with Class I and Class II liquids and shall comply with CFC Section 7903.
MONITORING:
The following procedures are required for monitoring:
1. Electronic leak detection that complies with California Code of Regulations (CCR) Title 23-
2634, shall be required to monitor the interstitial space between the primary and secondary tank.
2.All visible exterior surfaces of an aboveground storage tank, including any visible horizontal
surface directly beneath the tank, shall be inspected at least daily by direct viewing. The
inspection schedule shall be established such that some of the inspections are conducted when
the liquids are at their highest level.
3. A written statement of the routine monitoring procedures shall be available at the facility and
the record shall include the frequency of visual inspections,the locations) from which
02ord/chap 17-55f re/8115102 9
Ord.No.3571
observations will be made,the name(s) and title(s) of the person(s) responsible for performing
the observations and the reporting format.
4. Written records shall be maintained on site for three (3) years.
PRODUCT DISPENSING: Dispensers shall be equipped with a listed emergency breakaway
device designed to retain liquid on both sides of the breakaway point. The devices.shall be
located at each end of the hose between the nozzle and the pump. Such devices shall be installed
and maintained in accordance with manufacturer's instructions. (See NFPA (TIA) 30)
DISPENSING: Dispensers shall be equipped with a permanently attached, approved pumping
device mounted on top of tank, with an approved hose of an approved length for filling vehicles,
equipment or containers. Each tank shall have a pump that is activated/deactivated when the
nozzle is removed and replaced. (CFC Section 7903)
PIPE, VALVES, FITTINGS: In addition to other requirements outlined in CFC Section 7901.11,
the following shall be required:
Piping: All piping shall be enclosed in two (2) hour fire protection. Pipes containing liquid are
required to be double contained. This includes the base of working and emergency vents and fuel
sleeves. Manifold piping to connect multiple tanks is prohibited.
A fusible link valve, of the type that upon heat activation the valve will close preventing fumes
from ignition,.shall be required on all openings other than working and emergency vents. The
valve shall be approved by the Fire Chief
A fire extinguisher with a minimum classification of 2-A, 20 B:C shall be provided and so
located that it will be not more than seventy-five (75) feet from any pump, dispenser or fill pipe
opening. (See CFC Section 5202.9)
TANK LINING:
Tank linings are prohibited in the City of Huntington Beach unless approved by the fire chief.
(See CFC Section 7902.1.8.2.9).
SUPPORTS AND FOUNDATIONS:
Tanks shall rest on foundations made of concrete, masonry,piling or steel. Tank foundations
shall be designed to minimize the possibility of uneven settling of the tank and to minimize
corrosion in any part of the tank resting on the foundations. Steel tank supports shall be designed
to U.L. Standard 1709. (See CFC Section 7902.1.16)
ANCHORAGE:
Design of Supports: The design of the supporting structure for tanks shall be in accordance with
well established engineering principles in accordance with the Building Code.
02ordlchap E 7-55fire/8/15/02 10
Ord.No.3571
1. Tanks shall be so supported as to prevent the excessive concentration of loads on the
supporting portion of the shell. (See CFC-Section 7902.1.16)
2. Locations Subject to Flooding: Where a tank is located in an area that may be subjected to
flooding,the applicable provisions of CFC Appendix II-B apply.
3. Seismic Design: The tank supports and connections shall be designed to resist damage as a
result of such shocks in accordance with the Building Code. (See CFC Section 7902.1.12)
BARRIER PROTECTION:
Guard posts or other means shall be provided to protect exterior storage tanks from vehicular
damage specified as follows:
1. Seven(T) foot steel posts, with three (3') feet above and four (4) feet below grade. The post
shall be secured in a one (1) foot square concrete footing.
2. The post shall be of 112" steel (schedule 40) six (6") inch diameter and concrete filled with
cap.
3. The posts shall be thirtysix (36") inches apart on center.
4. The backside of the post shall be a minimum of three (T) feet from the tank.
DIKING:
The area surrounding a tank or group of tanks shall be provided with drainage or shall be diked
to prevent accidental discharge of liquid from endangering adjacent tanks, adjoining property or
reaching waterways.
Exception: When double containment is provided within the construction of the tank, the diking
requirements may be waived by the fire chief. (See CFC Section 7902.2.8)
VEHICULAR APPROACH PAD:
A nonabsorbent surface sufficiently covering the vehicle fueling area is required as approved by
the fire chief.
TANK VENTING AND VAPOR RECOVERY:
1. Emergency relief venting shall.be in accordance with CFC Section 7902.2.6 and NFPA (TIA)
30A. Emergency relief vents for gasoline primary and secondary tanks shall have a flame
arrestor as approved by the fire chief.
62ord/chap 17-55fire/8/15/D2 11
s
Ord.No.3571
2. A coaxial breakaway device as approved by the Fire Chief shall be required on phase II vapor
recovery systems. Vapor recovery shall be in accordance with CFC Section 5202.13 and the Air
Quality authority having jurisdiction.
APPROVED WIRING:
All installation of electrical wiring and equipment shall be reasonably safe to persons and .
property. For Class I liquids where electrical wiring and equipment installed, evidence that such
wiring and equipment are of the type approved for use in the hazardous locations as set forth in
CFC Table 5202.E-A and that such wiring and equipment have been installed in accordance with
the Electrical Code will be required. (See CFC Section.5202)
ELECTRICAL CONTROLS:
Emergency and routine electrical controls shall comply with the following:
1. A clearly labeled manually operated pump master switch shall be provided in an approved
location,within seventyfive (75') feet of, but not nearer than fifteen(15'.) feet to any dispenser.
2. Signs identifying the pump master switch shall be clearly labeled "EMERGENCY PUMP
SHUTOFF" in four (4") inch high letters with 1/2" strokes.
3. Where such master switch is not visible from all dispensers, the location thereof shall be
indicated by approved signs..
4. A control switch or each individual pump circuit switch shall be set in the "off' position at
time of business closure.
SAFETY RULES:
The following safety regulations shall be strictly enforced:
I. There shall be no smoking or open flames in the areas used for fueling, servicing internal
combustion engines, receiving or dispensing of Class 1, 11, or IIIA liquids.
2. There shall be no dispensing into unapproved containers. (See CFC Section 5201.6)
3. The engines of all vehicles being fueled shall be stopped. Conspicuous signs prohibiting
smoking,prohibiting dispensing into unapproved containers and requiring vehicle engines to be
shut off during fueling operations.shall be posted at each dispenser.
4. Flammable or combustible liquids or any waste liquid containing crude petroleum or its
products shall not be discharged into or upon any street, highway drainage canal or ditch, storm
drain, sewer, floodcontrol channel, lake or tidal waterway, or upon the ground.
5. Storage is prohibited on top of the tank(s).
02ord/chap l 7-55fire/8/15/Q2 12
Ord.No.3571
TANK IDENTIFICATION:
Aboveground storage tanks over 100 gallons (water capacity) permanently installed, mounted or
affixed and used for the storage of Class I, II or IIIA liquids shall bear the label or placard in
accordance with CFC Standard 793 identifying the material within- Aplacard shall also be
installed, mounted or affixed adjacent to the "Emergency Shutoff' sign.
TANK FILLING OPERATIONS:
Delivery operations shall comply with applicable requirements of NFPA 385, Standard for Tank
Vehicles for Flammable and Combustible Liquids.
1. The delivery vehicle shall be separated from any aboveground tank by at least twentyfive (25')
feet (7.6m). Tank filling shall not begin until the delivery operator has determined tank ullage
(available capacity). The delivery hoseline shall not exceed fifty(50') feet.
2. A dry Freak coupling shall be installed at a point where connection and disconnection is made
from the delivery vehicle to any aboveground tank. This device shall be protected from
tampering and physical damage. A sign stating "Do not remove or tamper with the Dry Break
Coupling" shall be affixed adjacent to the coupling.
3. An overfill-protection system approved by the fire chief is required. The tank shall be
equipped with an overspill box to contain any spill at the fill opening during delivery operations.
(See NFPA 30A CFC Section 4.3.3.4)
TESTING:
All tank and piping shall be tested in a manner acceptable to the Fire Chief. (See CFC Section
7901.11.10)
FENCING:
Fencing shall be provided for all installations. Fencing shall not be less than six (6) feet in
height, constructed of wire mesh, solid metal sheathing or masonry. Fencing shall be so located
as to provide protection from tampering or trespassing.
Exception: Tanks are not required to be enclosed within a fence if the property on which the
tanks are located already has a perimeter security fence. (See CFC Section 7902.3.5)
MAINTENANCE TESTING:
The integrity of the primary and secondary tanks shall be tested annually or after a significant
event or possible breach of integrity, by the tank owner or operator using the tank monitoring
port. All test results shall be maintained on the premises for three (3) years and shall be made
available to the fire chief upon request. (See CFC Section 7902.6.13)
02ord/chap 17-55fire/8/15/02 13
Ord.No.3571
The tank integrity tests at a minimum shall:
1. Test for vapor in the interstitial space.
2. Secondary tank vacuum or pressure procedure approved by the fire chief.
COMMUNICATIONS:
During hours of operation, the system's site shall be provided with a fire alarm transmitting
device. Such a device may be a telephone that is readily available. (See CFC Article 52)
SUPERVISION:
Where dispensing of Class 1, 11, or IIIA liquids is performed a listed automatic-closing type
nozzle valve shall be used incorporating the following features:
(See CFC Section 5202.4.4.2)
1. The hose nozzle valve shall be equipped with an integral latch-open device.
2. When the flow of product is normally controlled by devices or equipment other than the
nozzle valve, the hose nozzle valve shall not be capable of being opened unless the delivery hose
is pressurized. If pressure to the hose is lost, the nozzle shall close automatically.
Exception: Vapor recovery nozzles incorporating Insertion Interlock devices designed to achieve
shutoff upon disconnection with vehicle fill pipe.
3. The hose nozzle shall be designed in such a way that the nozzle is retained in the fill pipe
during the filling operation.
4. Supervision: The dispensing of Mass I and Class II liquids into a fuel tank of a vehicle or into
a container shall at all times be under the supervision of a qualified attendant.
Exception: Supervision by a qualified attendant is not required at locations,provided the owner
or operator provides and is accountable for:
a. At least daily site visits.
b. Regular equipment inspection and maintenance.
c. Conspicuously posting instructions for safe operation of dispensing equipment.
d. Posting the phone number of the owner operator.
e. A sign in addition to that required in CFC Section 5201.6.3 is posted in a conspicuous location
stating:
02ord/chap 17-5 5f re/8/15/02 14
......... ........ ...... ... ..
Ord.No.3571
ON CASE OF FIRE OR SPILL
1. Use Emergency pump shutoff
E 2. Report the accident
--- - - ........ ................
._...
FIRE DEPARTMENT#: 911
FACILITIES ADDRESS
f. Product delivery hoses from dispensers shall be equipped with a listed emergency breakaway
device designed to retain liquid on both sides of the breakaway point. Such doublebreakaway
devices shall be installed and maintained in accordance with manufacturer's instruction.
17.56.080 CFC Section 5202.4;5„Dispensing Supervision. CFC Section 5202.4.5 Delete 91 and
Delete#2.
17.56.085 CFC Section 6106.3 Portable Unvented Oil-Burning Heating Appliances. CFC
Section 6106.3 Location line 3 delete group S, Division 3, 4, and 5.
17.56.086 CFC Section 7503.1.3.7 AMEND Testing. Piping of systems shall be tested and
proven free of leaks after installation as required by the standards to which they were designed
and constructed. Test pressures shall not be less than 150 percent of the maximum allowable
working pressure when hydraulic testing is conducted or 110 percent when testing is conducted
pneumatically.
17.56.087 CFC Section 7901.3.2 Hazardous Materials Storage PI an. CFC Section 7901.3.2 is
Amended to Read: Plans. All new facilities and modifications to existing facilities proposing to
store, dispense, use or handle flammable or combustible liquids, shall submit a hazardous
materials storage and use plan in accordance with CFC Section 8001.3.2.
17.56.095 CFC Section 7902.2.2.1 Locations Where Aboveground Tanks Are Prohibited.
Restricted Locations. The limits referred to herein prohibiting the storage of Class I and II liquids
in outside, aboveground tanks are hereby established for all commercial land use districts as
defined in the Huntington Beach Zoning and Subdivision Ordinance.
EXCEPTIONS:
A. Bulk plants may exist in IG (general industrial) zoned districts only.
B. Class III liquids may only be stored on properties with a 0 or 01 suffix.
C. Class II liquids may be stored temporarily on construction sites with the approval of the fire
chief.
02ord/chap l 7-55 firel&115/02 15
Ord.No.3571
D. The storage of Class I and Class II liquids in aboveground tanks is prohibited within the City
of Huntington Beach except at locations classified as Zone IG (general industrial) where
permitted by a site plan use permit on property designated as potentially suitable for the uses
permitted under these zone classifications by the Huntington Beach Zoning and Subdivision
Ordinance as the same may be amended from time to time.
17,56.100 CFC Section 7902.6.3 Location of Underground Fuel Tanks. CFC Section 7902.6.3 is
amended to read as follows:
4. The installation of underground combustible/flammable liquid tanks is hereby prohibited in all
residential districts. The fire chief may authorize installation of underground
ombustible/flammable liquid tanks in agricultural and manufacturing districts.
17.56.105 CFC Section 7.902.6.10 Tank Lining. Tank linings are prohibited unless approved by
the Fire Chief.
17.56.110 CFC Section 7903.2.1.4 Heating, Cooking, and Lighting Devices. CFC Section
7903.2.1.4 Delete the exception.
17.56.115 CFC Section 7903.2.3.4.2 Mechanical Ventilation. CFC Section 7903.2.3.4.2 Delete
the exception.
17.56.120 CFC Section 7904.3.2.3 Oil Well Drilling and Operation. The distances set out in this
CFC Section 7904.3.2, at the discretion of the fire chief,may be reduced if added fire protection
is provided by installation of approved fire protection systems and devices.
17.56,130 CFC Section 7904.3.4.2 Sumps,-Backf lling. Backfilling Sumps. The maintenance of
any sump or other basin for the retention of oil or petroleum products in the City is prohibited.
17.56.135 CFC Section 7904.3.10 Huntington Beach Oil Code. The Huntington Beach Oil Code
(Huntington Beach Municipal Code Chapter 15.04) is incorporated herein by reference, and
declared to be part of the Huntington Beach Fire Code as though set out in full herein.
17.56.140 CFC Section 8001.3.2 Hazardous Materials Management Plan. Hazardous Materials
Management Plan. Compliance with Huntington Beach Municipal Code Chapter 17.58 requiring
a business emergency plan shall be considered in compliance with CFC Section 8001.3.2 except
as provided in CFC Section 8001.3.2.1 below:
8. In addition to the requirements set forth in CFC Section 8001.3.2, all new facilities and
existing facilities proposing modifications to handle or propose to handle hazardous materials
shall submit a hazardous materials storage and use plan packet. Packets/plans shall be submitted
and approved prior to installation and/or operation for all hazardous materials and each
application.
17-56.145 CFC Section 8001.3.3 Amended-Hazardous Materials InventoryStatement.
Deleted and amended to read:
02ord1chap l 7-55 fire/8/15102 16
Ord.No.3571
Hazardous Materials Inventory Statement. Compliance with Huntington Beach Municipal Code
Chapter 17.58 shall be considered in compliance with this section.
17.56.155 CFC Section 8001.5.2.2 Notification. Notification- The fire chief shall be notified
immediately when an unauthorized discharge becomes reportable under state, federal and
location regulations and in accordance with Huntington Beach Municipal Code Chapter 17.58,
17.56.165 CFC Section 8001.5.2.5 Responsibility For Cleanup (Soil Spec.) Clean-up of
contaminated soil and property shall be in accordance with state, federal or local regulations as
follows:
1. 1 st Clean-Up Criteria. Soils sampled during site assessments that fail California Assessment
Manual (CAM) criteria for hazardous waste will be excavated and disposed of at a proper
disposal site. Laboratory tests used in this determination are pH (EPA9045), CAM Metals (total),
and Volatile Chlorinated and Aromatic Hydrocarbons (EPA-8240) as described in item 6 below,
Site Assessment and Laboratory Specifications.
2. 2nd Clean-Up Criteria. Comparison of the total petroleum hydrocarbons (TPH) concentration
in soils sampled during the site assessment shall be made with the screening criteria in CFC
8001.5.2.5 Table I. If the sample results meet the Table 1 criteria, no further testing or
remediation work will be required.
If the TPH exceeds the screening criteria, the laboratory will perform the additional analyses
specified (EPA8020, EPA8270). Further delineation of the contaminated soil through use of
additional borings, additional trenches or by excavation and stockpiling must be performed to
determine the lateral and vertical extent of soil exceeding Table 1 criteria. Samples obtained
during this delineation will be analyzed for screening criteria listed in Table I (EPA418.1 and
EPA8015). If sample results exceed the screening criteria in Table 1, the laboratory shall be
instructed to run the analyses specified in CFC 8001.5.2.5 Table 2 (EPA8020, EPA8270)unless
the applicant chooses to excavate the contaminated soil to meet criteria in Table I without
proceeding to further analyses specified in Table 2. Soils which contain less than the screening
levels specified in Table 2 shall not be required to undergo soil remediation provided that EPA
418.1 and EPA 8015M Total Petroleum Hydrocarbon concentrations are less than 100% excess
of Table i screening criteria levels.
3. Depth,of Contaminated Soil Removal. Soil contamination in excess of the CFC 8001.5.2.5
Tables I and 2 criteria extending deeper than twenty (20) feet below ultimate finished grade or
within five (5) feet of the groundwater table, whichever is shallower, and not exhibiting
characteristics of material considered hazardous for disposal purposes may be considered for
non-remediation. Approval for non-remediation shall be by certification of the Fire Department
and shall be issued with appropriate findings. The lateral and vertical extent of this contaminated
material left in place shall be determined using Table I criteria. This extent shall be reported to
the City and disclosed to subsequent property owners in a format approved by the Fire
Department.
02ord/chap l 7-55 fire18I15/02 17
Ord.No.3571
Surface structures within one hundred(100) feet of the lateral extent of the contaminated soil
shall be built with vapor barriers in accordance with applicable City specifications.
4. Disposition of Stockpiled Soil. Soil that is stockpiled on site as a result of criteria applied
above can be evaluated for reuse on site. The reuse options may include, but are not limited to,
on site remediation and resampling to meet the criteria in CFC 8001.5.2.5 Table 1 and/or 2 or
reuse of the soil as road subgrade where applicable. Specifications for reuse of crude oil
contaminated soil as road subgrade are identified in item 7 below.
Soil that is planned for reuse on site should be sampled at a frequency sufficient to adequately
characterize the degree and composition of the contamination. A sampling plan shall be
submitted to the Fire Department for approval prior to reuse.
5. On Site Remediation. Soil can be remediated on site as long as it does not exhibit any
characteristics of material considered hazardous for disposal purposes. On site remediation must
comply with all applicable state, county, federal and city regulations. Remediation activities shall
be performed within a designated area. A remediation plan shall be approved by the Fire
Department.
After soil is remediated and reused, the surface of the designated remediation area shall be tested
in accordance with provisions identified herein above. A testing plan shall be submitted to the
Fire Department for approval as well as a final report which shall summarize the remediation
efforts and post remediation test results.
6. Site Assessment and Laboratory Specifications. Analyses performed during site assessments
of oil fields (other industrial or agricultural uses may require additional analysis) should include
pH (EPA9045), CAM Metals (total only, soluble if total exceeds ten times (STLC), Volatile
Hydrocarbons (EPA8240), Total Recoverable Hydrocarbons (EPA418.1), Total Fuel
Hydrocarbons (EPA8015), Semi-Volatile Organics (EPA8270) and Polychlorinated Biphenyls
(EPA8080).
Vertical limits of hydrocarbon contamination shall be assessed. Sampling shall extend to a depth
sufficient to identify at least five (5') feet of uncontaminated soil or to a depth not greater than
five (5') feet above the water table in cases where regional groundwater will be impacted by
sampling operations.
If the landowner chooses to cleanup the site using screening criteria specified in HBFC
8001.5.2.5 Table 2, the laboratory analytical work may specify the reanalysis of samples
exceeding screening criteria specified in HBFC 8001.5.2.5 Table 1. The shelf life for the
samples must not be exceeded when the reanalyses are run.
The laboratory contract shall specify use of EPA Method 3630 as a cleanup procedure prior to
soil analysis for CAPNA's using EPA8270 if the 418.1 results show greater than 1,000 ppm.
Samples representative of a specific site should be obtained consistent with a Phase 1 historical
review of the site. The sampling frequency will vary depending on potential for on site
02ordlchap 17-55fire/8115102 18
Ord.No.3571
contamination. Sampling should be targeted at identified or suspected contaminated locations on
the site.
Sampling of areas not suspected to be contaminated shall be done on a random basis according to
a Sampling Plan which shall be approved by the Fire Department.
The Sampling Protocol,both in terms of site specific targets and other random sampling should
be formulated in cooperation with the Fire Department. The burden of demonstrating soil
cleanup to established limits of contamination shall be the responsibility of the land owner. The
Fire Department's approval of a Sampling Protocol shall be required.
A Site Auditor, as identified in CFC 8001.5.2.5 shall be a requirement placed on all significantly
large oil field properties and on smaller properties where a reasonably large number of
contamination sources are deemed to remain unsampled following completion of the approved
Sampling Protocol. The requirement for a Site Auditor shall be at the discretion of the Fire
Department.
Soil sampling shall be carried out using protocols approved by the California Leaking
Underground Fuel Tank Manual and/or the Orange County Health Department.
Analytical results which may be inconsistent or anomalous when compared to other sample data
taken as part of the site assessment shall be made a part of the record although the land owner
shall have the option of providing additional samples to clarify inconsistencies. The number and.
location of hese samples shall be determined by the land owner.
7. Specifications for Reuse of Crude Oil Contaminated Soils as Road Subgrade. Soils must meet
criteria listed in HBFC 8001.5.2.5 Table 1 and 2.
Reused soils must meet compaction requirements.
Reused soils shall be placed directly beneath the asphalt cap and underlying aggregate to a
maximum depth of four(4) feet below the road surface. Fills deeper than four(4) feet must be
approved by the Fire Department based on sufficient findings.
Potable drinking water lines must be surrounded by clean sand or gravel and approved and
inspected by the appropriate City Departments before burial in the roadway.
A detailed set of drawings must be submitted to the City showing the plan of reused soils, a cross
section of the road base, locations of utility lines and thickness of clean sand and gravel pack
placed around these lines. Soil analysis data for the road fill must also be submitted which shall
verify compliance with the standards listed in Table 1 and/or Table 2.
8. Scope of Contract Specifications for On Site Auditing During Grading Activities.The Auditor
shall be an independent environmental or geotechnical consulting company with adequate
training to identify petroleum contaminated soils with field instruments and techniques described
02ord/chapl7-55firc/8/15/02 19
Ord.No.3571
below. The Auditor shall be licensed by the State of California as a Registered Environmental
Assessor.
Auditors will monitor grading activities for indicators that petroleum hydrocarbons may have
contaminated the soils and shall be aware of the situations and procedures:
a. Soft spongy soils that become evident as heavy equipment travels over it.
b.Hydrocarbon odors emanating from the soil.
c. A reading of greater than twenty(20) ppm on a hand held organic vapor monitor (OVM) held
three (3) inches from suspected contaminated soils. The meter shall be calibrated at least twice
per day.
d. A small vial of solvent can be used to extract a small amount of soil. If the solvent becomes
discolored petroleum may be present.
If any of the indicators above are found,the Auditor shall devise a sampling program capable of
ascertaining whether or not waste is classified as hazardous. All sampling procedures shall be in
accordance with the protocols established by LUTF and/or the Orange County Health
Department. The contamination citing shall be made a part of the record and the Fire Department
shall be immediately notified.
Sufficient samples shall be analyzed to characterize the vertical and horizontal extent of the
potential contaminant. If samples exceed the screening criteria in HBFC 8001.5.2.5 Table 1, the
soil must either be removed or reanalyzed and compared to criteria in HBFC 8001.5.2.5 Table 2.
If the soil is determined to meet the Table 2 criteria, the soil can be incorporated into the fill. If it
does not, the soil can be stockpiled for remediation and reuse or removed from the site.
A report documenting the observations made and samples obtained during grading shall be
prepared. This report shall document compliance with the appropriate section of Table 1 and/or
Table 2, as applicable.
Table 1 I
Screening Level for Hydrocarbon Cleanup '
Land Use TPH (418 1) TPH (8015M)
_
Residential &Recreational <500 ppm W < 500 ppm
_ ..0
Commercial & Industrial <1,000 ppm <1,000 ppm
Roadway
❑OW Below Road Surface n/a
<1,000 ppm total; <I00 ppm of
the<C14 component �
❑>4 Below Road Surface <1,000 ppm <1,000 ppm
02ordlchap 17-55fire/8/15/02 20
Ord.No.3571
Table 2
Screening Level for Hydrocarbon Cleanup
Land Use BTX & E 8020 PNA 8270 '
E. . . ( _� ... �-c . )_
Residential & Recreational B<1.0 ppm Each CAPNA<0.5 ppm
T, X & E <10.0 ppm Total CAPNA's <3.0 ppm
individually
FCommercial &Industrial B<1 0 ppm Each CAPNA<1 0 ppm
..... -
T, X & E <10.0 ppm ;Total CAPNA's <6.0 ppm
individually
Roadway �;
0'4' Below Road Surface B<1.0 ppm Each CAPNA <1 A ppm
r
X &E<10.0 ppmuallyTotal CAPNA's <9.0 ppm
divid ...._..._
>4' Below Road Surface FB<1.0 ppm Total CAPNA <1.0 ppm
-
T..................... , X& E <10.0 ppm Total CAPNA's <6.0 ppm
indlvldually
_ _...
['Based on CAPNA's found in Proposition 65 list, in addition to benzo (g,h,i) perylene]
17.56.170 CFC Section 8001.7 Identification Signs.
Identifications Suns. When required by the fire chief, visible identificaton signs shall be placed
in approved locations where hazardous materials are stored, dispensed, used or handled in
accordance with Huntington Beach Fire Prevention Division Hazardous Materials Identification
Guidelines City Specification 4423.
17.56.175 Add CFC Section 8003.1.3 Spill Control, Drainage Control, and Secondary
Containment.
Spill Control, Drainage Control, and Secondary Containment. Spill control, drainage control and
secondary containment in accordance with CFC Section 8003.1.3 may be required for those
amounts under the exempt quantities specified in CFC Section 8001.15 and Tables 8001.15-A
through 8001.15-D if deemed necessary by the Fire Chief.
17.56,180 CFC Section 8001.15.1 Exempt Amounts. Storage, dispensing, use and handling of
hazardous materials in quantities not exceeding exempt amounts shall be in accordance with
CFC Section 8001. At the discretion of the fire chief, hazardous materials present below the
exempt amounts specified in CFC Section 8001.15 and Tables 8001.15-A through 8001.15-D
may be required to meet provisions found in CFC Section 8003.1.
17.56.182 CFC Section 8003.1.2 Hazardous Materials Suns. CFC Section 8003.1.2 is amended
to read: Si ns. Stationary aboveground containers and tanks shall be placarded and labeled in
02ord/chap P-55fire/8/15/U2 21
f
Ord.No.3571
accordance with CFC Section 8001.7 and Huntington Beach Fire Prevention Division Stationary
Tank Hazard Identification Guidelines, refer to City Specification#423.
17.56,184 CFC Section 8003.1.5 Maximum Quantity Hazardous Materials On Site. CFC Section
8003.1.5 is amended to read: Maximum Quantity On Site. The storage of hazardous materials
shall be in accordance with local zoning regulations except as follows:
No person shall use or store extremely hazardous substances within a residential zoned or any
property developed for residential use.
EXCEPTION: The use of fumigants, pesticides, or other regulated economic poisons, when used
in accordance with nationally recognized standards by a State licensed contractor or the City and
for which a permit has first been issued by the Fire Chief.
17.56.190 CFC Section 8004.1.1 Applicability. At the discretion of the fire chief, materials
present below the exempt amounts set forth in CFC Section 8001.15 may be required to meet
provisions stipulated in CFC Sections 8004.1.2 through 8004.4.3.
17.56,192 UFC Section 8004.1.9 Hazardous Materials Signs.
Signs. In addition to the hazards identification signs required by UFC Section 8001.7, additional
hazard identification and warning signs shall be provided as follows:
Stationary containers and aboveground tanks shall be placarded and labeled in accordance with
Huntington Beach Fire Prevention Division Stationary Tank Hazard Identification Guidelines,
refer to City Specification 4423.
1756.195 CFC Section 8102.10.2 Hi>7h Piled Stock Aisle Width. CPC Section 8102.10.2 is
amended to read as follows: ^
During the stocking operation, a minimum exit width of fortyfour (44) inches shall be
maintained.
CFC Section 8102.10.2.1 to read as follows:
3. Exceptions: When cross aisles are provided the maximum required width shall be fourteen
(14) feet.
17.56.200 Adopt CFC Appendix IA AmendedLife safety requirementsfor existing buildings
other than high rise.
Section 1. GENERAL
EXCEPTION: Group R, Division 1 (less than seven (7) units), Group U occupancies and
occupancies regulated by Appendix I and Group R, Division 3 Occupancies, except that Group
R, Division 3 Occupancies will comply with Section 6.
02ord/chapl7-55fire/8/15/02 22
Ord.No.3571
17.56.205 Adopt CFC Appendix II-C Amended Marinas.
Section 2. PLANS AND APPROVALS GENERAL.
Plans for marina fire-protection facilities shall be approved by the Fire Chief prior to installation.
The completed work shall be subject to final inspection and approval after installation.Two (2)
sets of plans shall be submitted to the Fire Department indicating:
(a) The dock layout.
(b) The location of wet standpipe outlets, accompanied by pipe schedules and hydraulic
calculations.
(c) Location of fire extinguisher cabinets.
Section 6. FIREPROTECTION EQUIPMENT.
All piers, wharves, floats with facilities for mooring or servicing five (5) or more vessels, and
marine service stations shall be equipped with fire protection equipment as follows:
(a) A wet standpipe system shall be installed on all docks, piers, wharves, or marine service
stations that exceed one hundred (100)feet in length or are otherwise inaccessible from City fire
hydrants. The wet standpipe system shall be capable of delivering two-hundred and fifty (250)
gallons per minute at a residual pressure of fifty(50) PSI at the outlet. The outlet shall be a two-
and-one-half(2 1/2) inch national standard thread with an approved gate valve. Outlets shall be
spaced at two hundred (200) foot intervals, in approved locations, preferably at point of public
access. Outlets shall be installed so that they are readily visible, unobstructed and readily
discernible as a piece of firefighting equipment.
(b) Piers and wharves shall be provided with fire apparatus access roads and water supply
systems with onsite fire hydrants as may be required by the fire chief. Such roads and water
systems shall conform to CFC Article 10 of this code.
(c)The wet standpipe system shall be provided with a Fire Department siamese connection
which shall be located within five (5) feet of the nearest fire apparatus access roadway.
(d) PORTABLE FIRE-PROTECTION EQUIPMENT.
(1) A 4 -A, 40B:C fire extinguisher shall be located every one hundred and fifty (150) feet along
the dock. The fire extinguisher shall be located in a standard fire extinguisher cabinet with a
breakable glass front. The Cabinet shall have placards on both sides with the words 'FIRE
EXTINGUISHER' and either have an additional placard on the front or shall be easily
recognized from the front as a fire extinguisher cabinet.
(2) The Fire Chief shall designate the type and number of all other fire appliances to be installed
and maintained in each marina.
02ord/chap 6 7-55f re18/15102 23
. ........................................... ............. ..... ...
Ord.No.3571
7. TRANSMISSION OF ALARMS.
A means for transmitting alarms immediately to the Fire Department shall be available pursuant
to the standards and specification of the Huntington Beach Fire Department. ws
17.56.210 Adopt CFC Appendix IIE AmendedHazardous Materials Management Plan and
Hazardous Materials Inventory Statement.
Section 1. Scope
x ,
The Huntington Beach Municipal Code, Chapter 17.58 is incorporated herein by reference, and
declared to be part of the Huntington Beach Fire Code as though set out in full herein. The intent
of Appendix IIE and Municipal Code Chapter 17.58 is deemed to be substantially equivalent in
intent.
17.56.220.Adopt CFC Appendix IIK AmendedAboveground Tanks Appendix II-K Section 4.3
Tank Design- Size: Primary tanks shall not exceed a 2,200 gallons maximum tank, the aggregate
gallonage per site shall be limited to 2,200 gallons.
Quantities greater than 2,200 gallons aggregate shall be approved by the fire chief.
Rest of Page Intentionally Left Blank
02ord/chap l 7-55fire/8/15/02 24
Ord.No.3571
Table A-11-1 - Minimum Separation Requirements For NonProtected Aboveground Tanks
E
E MINIMUM
DISTANCE FROM .
MINIMUM E THE NEAREST SIDE
DISTANCE FROM OF ANY PUBLIC
PROPERTY LINE WAY OR FROM THE;
NEAREST
WHICH CAN BE IMPORTANT
BUILT UPON,
INCLUDING THE BUILDING ON THE MINIMUM
INDIVIDUAL TANK SAME PROPERTY DISTANCE
` CAPACITY = OPPOSITE SIDE OF BETWEEN TANKS
A PUBLIC WAY Feet
Feet(mm)
mm
Gallons (liters) ( ) Feet (mm)
Less than or equal to 15 (4572) I S (4572) 3 (914)
2,200
15 (4572) 15 4572 3 914
SECTION 2. This ordinance shall become effective 30 days after its adoption.
PASSED AND ADOPTED by the City Council of the City of Huntington Beach at a
regular meeting thereof held on the 16th day of September , 2002.
Mayor -
ATTEST:
d�so1.i APPROVED AS TO FORM:
City Clerlc
City AttorneyIlN�6Z
REVIEWED AND APPROVED:
INITIATED AND APPROV D:
City AChinistrator
Fire. Chi.e /,Info Sys Director
25
02ordlchapl7-55fire/8114/02
Ord. No. 3571
STATE OF CALIFORNIA }
COUNTY OF ORANGE } ss:
CITY OF HUNTINGTON BEACH .)
1, CONNIE BROCKWAY, the duly elected, qualified City Clerk of the
City of Huntington Beach, and ex-officio Clerk of the City Council of said City, do
hereby certify that the whole number of members of the City Council of the City of
Huntington Beach is seven; that the foregoing ordinance was read to said City Council at
a r_e?ular meeting thereof held on the 19th day of August, 2002, and was again read to
said City Council at a regular meeting thereof held on the 16th day of September, 2002,
and was passed and adopted by the affirmative vote of at least a majority of all the
members of said City Council.
AYES: Green,Dettloff,Boardman,Cook,Houchen,Winchell,Bauer
NOES: None
ABSENT: None
ABSTAIN: None
I,Connie Brockway,CITY CLERK of the City of
Huntington Beach and ex-officio Clerk of the City
Council,do hereby certify that a synopsis ofthis
ordinance has been published in the Huntington Beach
Fountain Valley Independent on
2002
In accordance with the City Charter of said City City Clerk and ex-officio Clerk
Connie Brockway, City Clerk of the City Council of the City
Deputy City Clerk of Huntington Beach, California