HomeMy WebLinkAboutApprove a Sole Source Procurement Request to Purchase 3 Meed mi vi 6 -D-/
�(7R A-e.Ej
��NTtNGro' 2000 Main Street,
Huntington Beach,CA
„s F
City of Huntington Beach 92648
C_couNTY CP,
File#: 22-886 MEETING DATE: 11/15/2022
REQUEST FOR CITY COUNCIL ACTION
SUBMITTED TO: Honorable Mayor and City Council Members
SUBMITTED BY: Al Zelinka, City Manager
VIA: Sean Crumby, Director of Public Works
PREPARED BY: Rafael Suarez, Public Works Contract Administrator
Subject:
Approve a sole source procurement request to purchase 3 Meeder Ransome vaporizer units
to fuel backup generators for the water system's booster stations
Statement of Issue:
Staff requests City Council approval for a sole source procurement of three Meeder Ransome
vaporizer units to fuel backup generators for the water system's booster stations at a total cost of
$138,000. The City's current backup systems were built around the specifications of Meeder
Ransome vaporizer units, which are currently in use and operating well past their 10-year life cycle.
Replacing these aging units is a priority of the system. As such, the City requests a sole source
procurement to replace like for like, which will expedite the replacement process and preclude the
modification of the existing system to fit a comparable product at significant cost.
Financial Impact:
No additional funding is requested. Sufficient funds for the vaporizer units are budgeted in the FY
2022-2023 Water Supply Equipment Maintenance - Maintenance Booster Stations, Business Unit
50685803.67715.
Recommended Action:
Approve the sole source procurement request for the purchase of 3 Meeder Ransome vaporizer units
to fuel backup generators for the water system's booster stations.
Alternative Action(s):
Do not approve the recommended action, and direct staff accordingly.
Analysis:
The City's water system utilizes booster stations that serve the critical function of pressurizing the
system to deliver water to each of our customers. These booster stations must be properly
maintained and equipped, in order to function reliably every day. To ensure the continuous operation
City of Huntington Beach Page 1 of 2 Printed on 11/9/2022
powereelA Legrstar T""
File #: 22-886 MEETING DATE: 11/15/2022
of the booster systems, even during emergencies such as blackouts, each one is equipped with a
backup power system.
These backup systems rely on vaporizer units to transform liquefied petroleum gas (LPG) into a
vaporized gas that fuels the backup systems. Currently, the City utilizes Meeder Ransome vaporizer
units that were built in 1993 and are operating well past their planned 10-year life cycle, which is not
a best practice and requires replacement.
When the backup power systems were initially built, they were made to accommodate the
specifications of Meeder Ransome vaporizer units. While there are comparable units from other
manufacturers on the market today, incorporating and utilizing them would necessitate the
replacement of the backup system (including intake and discharge piping), estimated to cost
approximately $75,000 to $125,000 (in addition to the cost of the units themselves). Furthermore, a
replacement of the backup system will delay the replacement of the aging vaporizer units, which
creates a potential risk to the reliability of the water system. To minimize these risks, staff
recommends utilizing a sole source procurement of three replacement vaporizer units from Meeder
Ransome at a cost of$138,000. This includes the cost for Meeder Ransome to manufacture, deliver,
install, and provide training to operate the units. This action would not require any modifications to
the existing system to put the units into operation.
Environmental Status:
Not applicable
Strategic Plan Goal:
Infrastructure & Parks
A ttachment(s):
1. Sole Source Procurement Request for Meeder Ransome Vaporizer Units
City of Huntington Beach Page 2 of 2 Printed on 11/9/2022
powereel ,Legistarr"
CITY OF HUNTINGTON BEACH
Sole-Source Justification
Wire,o (For use on all goods and services acquisitions.)
This justification document consists of two(2)pages. All information must be provided and all questions must be answered. The"Required
Approvals"section must include a date for each signature,as appropriate for the transaction.
Requesting Department Information
Date: October 13, 2022
Requestor Name: Rafael Suarez Division Manager: Alvin Papa
(Type names. Do not sign.)
Department: Public Works Department Head: Sean Crumby
(Type names. Do not sign. Must be same as signature below.)
Department Contact Information
Contact Name: Chris Cassotta Street Address: 19001 Huntington Street
Telephone: 7143741512
Fax: Shipping Address: 19001 Huntington Street
Cellular phone: 7143194806
Required Contact Information
Contractor/Supplier Name: Meeder Ransome
Contractor/Supplier Address: 3495 South Maple Ave.
Contractor/Supplier City/State/Zip: Fresno, CA. 93725
Original Contract Amount:* Amendment Amount:* (if applicable) New Contract Amount:*
$138,000 $ $
(*Includes original contract and previously (*Includes original contract and all amendments,
approved amendments) (Current amendment only) including current amendment)
Provide a brief description of the acquisition, including all goods and/or services the contractor will provide:
Provide materials and labor to replace emergency back up fuel vaporizers for the city's water pressure boosting facilies.
Contract Type and Term
Contract Type: Contract Term: What account number will be used to purchase?
Select One: ❑ Goods Begin: N/A Business Unit: 506858036
❑ Service
Goods&Services End: N/A Object Code: 67715
Required Approvals
Department Hea. Fin ce Manager-Budget �Chi�f Financial Officer Assistant City Manager
�i� ;�v�ved ❑D:� 'prove ❑ Denied Ld'Approved ❑Denied pproved ❑Denied
O/// i
Signatur / ignature Signature Signature
1,0//Cr 7‘ I0/20/Zo�� 1o/2,t(z- 1 p/ �ZO?/L
Dat Date Date Date
(Transactions exceeding$50,000
must be approved by City Council)
1
,i iNcro
`' `�",...... CITY OF HUNTINGTON BEACH
mot, -Ni,
v.�= . „°' Sole Source Justification
F'•.........`A0
'coU"v o!," (For use on all goods and services acquisitions.)
Complete responses must be provided for all of the following items.
A. THE GOOD/SERVICE REQUESTED IS RESTRICTED TO ONE SUPPLIER FOR THE REASONS STATED BELOW:
1. Why is the acquisition restricted to this goods/services/supplier?
(Explain why the acquisition cannot be competitively bid.)
Our system is customized specifically to the Meeder Ransome Vaporizer units. By replacing in kind with
updated models, it will save time and money.
2. Provide the background of events leading to this acquisition.
Inspection reports indicate our existing units were built in 1993 and are now 3 times beyond their normal
10-year service life; making them unsafe and unreliable.
3. Describe the uniqueness of the acquisition (why was the good/service/supplier chosen?).
The original water backup fuel supply system was built using Ransome Meeder's Vaporizer units. By
replacing in kind,there is no downtime, eliminating potential risk to the City's water system.
4. What are the consequences of not purchasing the goods/services or contracting with the proposed
supplier?
By not replacing in kind with Meeder Ransome's units it will require additional time and money used for
re-design, bid, award, and construction.To minimize risk,the vaporizer units require immediate
replacement. Delaying installation puts our water system at risk and may significantly impact water
service.
5. What market research was conducted to substantiate no competition, including evaluation of other items
considered?
(Provide a narrative of your efforts to identify other similar or appropriate goods/services,including a summary of how the department
concluded that such alternatives are either inappropriate or unavailable. The names and addresses of suppliers contacted and the reasons
for not considering them must be included OR an explanation of why the survey or effort to identify other goods/services was not performed.)
The research of price and availability of another manufacturers such as Algas-SDI indicated comparable
pricing. However, because our systems are custom fit with Meeder Ransome's units, using other
manufacturers would require special modifications which would result in voided warranties. Contacts
were made through Burnerparts.com 2011 Williamsburg Road, Richmond, VA 23231 and Algas-SDI 151 S.
Michigan St. Seattle, WA 98108
B. PRICE ANALYSIS
1. How was the price offered determined to be fair and reasonable?
(Explain what the basis was for comparison and include cost analyses as applicable.)
The price of Meeder Ransome's Vaporizers were determined to be fair and reasonable because it was
comprable to other manufactures but also offered customized installation to fit our current system,
warranty, and training not included by the others.
2. Describe any cost savings realized or costs avoided by acquiring the goods/services from this supplier.
By replacing in kind, we avoid having to pay engineering design, structure modification, and construction
costs which can range from approximately$75,000 to $125,000.
Remit completed form to: City of Huntington Beach—Purchasing Division
2000 Main Street,Huntington Beach,CA 92648-2702
3
Manufacturer/ Brand
Meeder Ransome Algas-SDI
2 x Vaporizer
Capcacity: 320 US Gal/h $88k $66k
1 x Vaporizer
Capcacity:40 US Gal/h $9k $11k
Installation $16k not offered
Training Included not offered
Design &Construction None $75k-$125k
Total (Excluding Tax) $113k $152k to$202k
eeder
LP-G IMd
Ransome
as Equipment and Manufacturing
3495 South Maple Avenue • Fresno,California 93725-2413 • PO Box 12446 Fresno,California 93777 2446
Telephone(559)485-0979 • (800)342-8265 • Fax(559)485-8869 • E-mail:office@needer.com • vvommeeder.com
09/27/22
City of Huntington Beach
19001 Huntington Street
Huntington Beach, CA 92648
Chris Cassotta & Rafael Suarez;
Thank you for the opportunity to bid the replacement of our equipment at your three
facilities. At your site on Huntington Street, we suggest you replace the PAMW180-10
with a PAM200-10, which is what you have at the Peck water retention site. The PAM
direct-fired unit is better for intermittent service such as what you expect for a back up
to natural gas. There is a cost savings as well.
Peck would also receive a new PAM200-10 as well. Edwards Hill will receive another
RH8OE vaporizer. The first stage regulator (627-7710) also needs to be replaced at the
same time and a small over-pressure relief valve should be added (P/N 1805-19P).
* Ransome PAM200-10E for the Huntington Street facility $43,725.00 net.
* Ransome PAM200-10E for the Peck facility $43,725.00 net.
* Ransome RH8OE / 627-7710 Regulator/ 1805-19P Relief $ 8,650.75 net.
Subtotal $96,100.75
Taxable items above @7.75% $ 7,447.81
Subtotal $103,548.56
* Installation labor, per diem and transportation $ 15,864.10 net.
$119,412.66 net total
Sincerely,
Arch Hudelson
Ransome Mfg.
Free shipping for most orders over $75 Most orders processed before 2:3o pm EST, ship same day
URNERPARTS.COM
YOU CAN'T BE COOL UNLESS YOU'RE RUNNIN'HOT
t
`Fyk 4' Afi
�.rvzyia`e
� Y
320H Direct Fired Vaporizer - Call for Pricing!
PRICE: $32,686.00 Item Code:320H
320 GPH/640 Kg/Hr/29 Mmbtu/hr
Product Documents
Quantity - 1 + add to cart
There are no file attachments for this product.
PrnrJrNCY Mtarhr r�tc
Product Description
Algas-SDI Direct Fired 320H LP Gas
Ideal for applications that lack electricity or requires portability
SPECIFICATIONS
VAPORIZATION TYPE Direct Fired/ Row Through
ELECTRICAL DATA nl..r,o Do.a iirr J
----...--..--..... I wi is noun cu
I.
MODEL NUMBER
320H
DESIGN PRESSURE 290 PSI / 20.0 Barg
RELIEF VALVE SET POINT 25o PSIG / 17.2 Barg
HYDROSTATIC PRESSURE 435 PSIG /29.9 Barg
VAPORIZER APPROVALS: ASME, UL(US and Canada)
LIQUID INLET(FNPT) 2"
LIQUID OUTLET(FNPT) 2"
VAPORIZATION CAPACITY 640 Kg/h
320 US Gal/h
29.1 MMBTU/h
BURNER INPUT 90.8 KcaL/h
360.0 BTU/h
BURNER IGNITION gvdc Re-ignitor standard on all units
SHIPPING WEIGHT 810 Lbs
368 kg
SHIPPING DIMENSIONS Length 43'
Width 48"
Height 72"
KEYTS
NOOELECTRICITY REQUIRED Operational Overview
AUTO RE-IGNITOR STANDARD
DOUBLE LIQUID CARRY-OVER
PROTECTION By design.OF series direct fired vaporizers apply heat directly to a pressure vessel containing liquid LPG.The heating
THERMOSTAT EASILY OPERATED process induces vaporization,while consuming a small amount of the vapor generated.OF series vaporizers ensure a
WITH GLOVES continuous vapor supply to your application.
EASY ACCESS INLET VALVE
LOW PROFILE (40/40 THRU 120/60) Algas-SDI vaporizers are build tough.A rugged heavy gauge motel enclosure with power coat applied over zinc plating
FOR EASE OF PORTABILITY protects against harsh environments.The stainless-steel exhaust flue and stainless-steel tubing eliminates potential
PROPRIETARY CAPACITY CONTROL clogging of the vaporizer's temperature controller and burner orifices.
VALVE PREVENTS LOCK UP
BURNER GAS ISOLATION VALVE
PROVIDED Access to the vaporizer internals is provided via A latch-less reliable door panel.The design allows easy removal of the
THERMOW ELL ALLOWS EASY burner if required.Our domed exhaust top combined with our unique flue collar design.prevents water rain infiltration to
REPLACEMENT OF GAS VALVE the burner.Algas-SDI Provides an automatic 9VDC re-ignitor as standard.When service requires replacement of the re-
"SNAP-IN"40/40 PILOT ASSEMBLY ignitor,spade connectors make the field change simple.Removal of the 9VDC battery allows the end user to disable the re-
ignitor.
t. PHONE CONTACT 0 E-MAIL CONTACT Q OFFICE LOCATION Q OFFICE HOURS
1804)236-38BI sa esfeburnerparts.com 2011 Williamsburg Road Mon-fri BAM-5PM EST
Richmond.VA 23231.USA
YOU CAN'T BE COOL UNLESS YOU'RE RUNNIN'HOT
URNERPARTS.IOM PRODUCTS INFORMATION SERVICE
CAN'T BE COOL UNLESS YOU'RE RUNNIN'HOT Lau tors About Us Account
Email:,S,..URDorJ Lburnerp arts.com Meters Delivery Information y y Orders
Phone:,(804) 236-3881 Pressure Switches FAQ S�R(�ingCar
!gam tors Privacy Policy Return Policy
Free shipping for most orders over $75 Most orders processed before z:3o pm EST. ship same day
AURNERPARTS
YOU CAN'T BE COOL UNLESS VANE RUNNIN'HOT
Bf
V AP
b MOM
�!1
I
80/40H Direct Fired Vaporizer
PRICE: $10,262.00 Item Code:80/40H
80 G PH/160 Kg/H r/7.2 M m btu/h r
Product Documents
Quantity - + add to cart
There are no file attachments for this product.
Prrr1i it f Attarhmentc
Product Description
Algas-SDI Direct Fired 80/40H LP Gas
Idol for opp ie.M.w det lock electricity r mires portability
SPECIFICATIONS
VAPORIZATION TYPE Direct Fired/ Flow Through
ELECTRICAL DATA nl...,rs o.,r1 .e.-J
- INV!IC fCHuii Cu
MODEL NUMBER 80/40H
DESIGN PRESSURE 2g0 PSI / 20.0 Barg
RELIEF VALVE SET POINT 250 PSIG / 17.2 Barg
HYDROSTATIC PRESSURE 435 PSIG /29.9 Barg
VAPORIZER APPROVALS: ASME, UL(US and Canada)
CE, PED (DNV)
LIQUID INLET(FNPT) 3/4"
LIQUID OUTLET(FNPT) 1'
VAPORIZATION CAPACITY 8o Kg/h
40 US Gal/h
3.6 MMBTU/h
BURNER INPUT 13.o Kcal/h
51.3 BTU/h
BURNER IGNITION gvdc Re-ignitor standard on all units
SHIPPING WEIGHT 155 Lbs
71 kg
SHIPPING DIMENSIONS Length 21'
Width 22"
Height 42"
KEYPOINTS Operational Overview
NOOELECTRICITY REQUIRED
AUTO RE-IGNITOR STANDARD
DOUBLE LIQUID CARRY-OVER
PROTECTION By WIpi.Of trio fret And veoerizers poly heat directly to a pressure vessel containing liquid LPG.The heating
THERMOSTAT EASILY OPERATED pia Ike"noerhetem adult ceoa uing a small amount of the vapor generated.OF series vaporizers ensure a
WITH GLOVES continuos o r as pply to yor application.
EASY ACCESS INLET VALVE
LOW PROFILE(40/40 THRU 120/60) Algae-SDI vaporizers re haiM tacclt A rented heavy page metal enclosure with power coat applied over zinc plating
FOR EASE OF PORTABILITY
PROPRIETARY CAPACITY CONTROL protect'�p herd���U. �exhaust flue end stainless-steel tubing eliminates potential
clogging of the vaporizer:temperature mntroler end boner orifices.
VALVE PREVENTS LOCK UP
BURNER GAS ISOLATION VALVE
PROVIDED Access to the vaporizer internals is provided via A latch-less reliable door panel.The design allows easy removal of the
TH ERMO W ELL ALLOWS EASY burner if required.Our domed exhaust top combined with our unique flue collar design.prevents water ram infiltration to
REPLACEMENT OF GAS VALVE the burner.Algae-SDI Provides an automatic 9YDC re-ignitor as standard.When service requires replacement of the re-
"SNAP-IN"40/40 PILOT ASSEMBLY ignitor.spade connectors make the field change simple.Removal of the 9VDC battery allows the end user to disable the re-
ignitor.
t,. PHONE CONTACT Ig E-MAIL CONTACT Q OFFICE LOCATION ®OFFICE HOURS
(8114)236-3881 atifiAMMITrim 2O1 f✓l gJ.ed Man-Fri IAM-5PM EST
R YA?V USA
YOU CAN'T BE COOL UNLESS YOU'RE RUNNIN'HOT
BURNERPARTS.COM PRODUCTS INFORMATION SERVICE
You CAN'T BE COOL UNLESS YOU'RE RUNNIN'HOT pggytators About Us Account
tmail:534RoortCa�burnerparts.com Meters Delivery Information My Orders
Phone:(804)236-3881 pressure Switches E9Q $hoopjng
Innitnrs Privacy Policy Return Policy